7
START AND STOP PROCEDURE
Mod. PAGURO
6000/9000/14000/18000/6500/8500
Date: 12.03.2020_Rev: 0.0
3
After the first 20 hours of generator operation, check the maintenance table (par. 10.3.7) for the correct
maintenance operations to be carried out.
7.4 STOPPING THE GENERATOR
To stop the generator, follow this procedure:
1. Remove the AC loads from the generator one at a time and allow the generator to run for an additional
3 to 5 minutes (this stabilizes its operating temperature).
2. Press the “STOP” button on the remote control panel to stop the generator. The shutdown is automatic;
3. Check the lube oil level a few minutes after stopping the engine, because lube oil from the bearings
etc. continues to drain down into the oil sump. Disregarding this fact and not maintaining the proper
oil level may lead to overfilling, causing overheating and the possibility of engine runway.
4. After shutdown, carefully inspect the generator. Check for possible leaks from all the connections
inside the sound-shield.
Control panel