Values are based on a typical motor efficiency (eff2/eff3 border line). Motors with lower efficiency will also add to the power loss in the
adjustable frequency drive and vice-versa.
If the switching frequency is increased compared to the default setting, the power losses may rise significantly.
LCP and typical control card power consumption values are included. Further options and customer load may add up to 30 W to the
losses. (Though typical, only 4 W extra for a fully loaded control card, or options for slot A or slot B, each).
Although measurements are made with state of the art equipment, some measurement inaccuracy must be allowed for (
±
5%).
5) The three values for the max. cable cross-section are for single core, flexible wire and flexible wire with sleeve, respectively.
PK75
P1K1
P1K5
P2K2
P3K0
P4K0
P5K5
P7K5
Typical Shaft Output (hp [kW])
1 [0.75]
1.5 [1.1]
2 [1.5]
3 [2.2]
4 [3]
5 [4]
7.5 [5.5]
10 [7.5]
Enclosure IP20, IP21
A3
A3
A3
A3
A3
A3
A3
A3
Enclosure IP55
A5
A5
A5
A5
A5
A5
A5
A5
Output current
Continuous (3x525–550 V) [A]
1.8
2.6
2.9
4.1
5.2
6.4
9.5
11.5
Intermittent (3x525–550 V) [A]
2.9
4.2
4.6
6.6
8.3
10.2
15.2
18.4
Continuous (3x551–600 V) [A]
1.7
2.4
2.7
3.9
4.9
6.1
9.0
11.0
Intermittent (3x551–600 V) [A]
2.7
3.8
4.3
6.2
7.8
9.8
14.4
17.6
Continuous kVA (525 V AC) [kVA]
1.7
2.5
2.8
3.9
5.0
6.1
9.0
11.0
Continuous kVA (575 V AC) [kVA]
1.7
2.4
2.7
3.9
4.9
6.1
9.0
11.0
Max. input current
Continuous (3x525–600 V) [A]
1.7
2.4
2.7
4.1
5.2
5.8
8.6
10.4
Intermittent (3x525–600 V) [A]
2.7
3.8
4.3
6.6
8.3
9.3
13.8
16.6
Additional specifications
IP20, IP21 max. cable-cross section
5)
(line
power, motor, brake and load sharing) [mm
2
(AWG)]
2)
4,4,4 (12,12,12)
(min. 0.2 (24))
IP55, IP66 max. cable cross-section
5)
(line
power, motor, brake and load sharing) [mm
2
(AWG)]
4,4,4 (12,12,12)
Max. cable cross-section
5)
with disconnect
6,4,4 (10,12,12)
Estimated power loss
at rated max. load [W]
4)
35
50
65
92
122
145
195
261
Weight, Enclosure IP20 (lb [kg])
14.33
[6.5]
14.33
[6.5]
14.33 [6.5]
14.33
[6.5]
14.33
[6.5]
14.33
[6.5]
14.55
[6.6]
14.55 [6.6]
Weight, enclosure IP55 (lb [kg])
29.76
[13.5]
29.76
[13.5]
29.76
[13.5]
29.76
[13.5]
29.76
[13.5]
29.76
[13.5]
31.31
[14.2]
31.31
[14.2]
Efficiency
4)
0.97
0.97
0.97
0.97
0.97
0.97
0.97
0.97
Table 10.7 Line Power Supply 3x525–600 V AC (FC 302 only)
Specifications
VLT
®
AutomationDrive Instruction
Manual
MG33AM22 - VLT
®
is a registered Danfoss trademark
10-7
10
10
Содержание FC 300
Страница 1: ...MAKING MODERN LIVING POSSIBLE Instruction Manual VLT AutomationDrive FC 300 0 25 75 kW ...
Страница 2: ......
Страница 8: ...Contents VLT AutomationDrive Instruction Manual MG33AM22 VLT is a registered Danfoss trademark ...
Страница 14: ...Introduction VLT AutomationDrive Instruction Manual 1 6 MG33AM22 VLT is a registered Danfoss trademark 1 1 ...
Страница 62: ...Status Messages VLT AutomationDrive Instruction Manual 7 4 MG33AM22 VLT is a registered Danfoss trademark 7 7 ...
Страница 109: ...Index VLT AutomationDrive Instruction Manual MG33AM22 VLT is a registered Danfoss trademark 12 5 ...
Страница 110: ...www danfoss com drives MG33AM22 130R0300 MG33AM22 Rev 2013 03 12 ...