2.
Scroll to parameter group 5-1*
Digital Inputs
and
press [OK].
130B
T769.10
5-0* Digital I/O mode
5-1* Digital Inputs
5-4* Relays
5-5* Pulse Input
14.7% 0.00A 1(1)
Digital In/Out
5-**
Figure 5.10
3.
Scroll to
5-10 Terminal 18 Digital Input
. Press [OK]
to access function choices. The default setting
Start
is shown.
5-1*
130B
T770.10
5-10 Terminal 18 Digital
Input
[
8
]] Start
14.7% 0.00A 1(1)
Digital Inputs
Figure 5.11
5.4 International/North American Default
Parameter Settings
Setting
0-03 Regional Settings
to [0]
International
or [1]
North America
changes the default settings for some
parameters.
lists those parameters that are
affected.
Parameter
International
default parameter
value
North American
default parameter
value
0-03 Regional
Settings
International
North America
1-20 Motor Power
[kW]
See Note 1
See Note 1
1-21 Motor Power
[HP]
See Note 2
See Note 2
1-22 Motor Voltage 230 V/400 V/575 V
208 V/460 V/575 V
1-23 Motor
Frequency
50 Hz
60 Hz
3-03 Maximum
Reference
50 Hz
60 Hz
3-04 Reference
Function
Sum
External/Preset
Parameter
International
default parameter
value
North American
default parameter
value
4-13 Motor Speed
High Limit [RPM]
See Note 3 and 5
1,500 RPM
1,800 RPM
4-14 Motor Speed
High Limit [Hz]
See Note 4
50 Hz
60 Hz
4-19 Max Output
Frequency
132 Hz
120 Hz
4-53 Warning Speed
High
1,500 RPM
1,800 RPM
5-12 Terminal 27
Digital Input
Coast inverse
External interlock
5-40 Function Relay No operation
No alarm
6-15 Terminal 53
High Ref./Feedb.
Value
50
60
6-50 Terminal 42
Output
No operation
Speed 4–20 mA
14-20 Reset Mode
Manual reset
Infinite auto reset
Table 5.1 International/North American Default Parameter Settings
Note 1: 1-20 Motor Power [kW] is only visible when 0-03 Regional
Settings is set to [0] International.
Note 2:1-21 Motor Power [HP], is only visible when 0-03 Regional
Settings is set to [1] North America.
Note 3: This parameter is only visible when 0-02 Motor Speed Unit is
set to [0] RPM.
Note 4: This parameter is only visible when 0-02 Motor Speed Unit is
set to [1] Hz.
Note 5: The default value depends on the number of motor poles. For
a 4 poled motor the international default value is 1,500 RPM and for
a 2 poled motor 3,000 RPM. The corresponding values for North
America is 1,800 and 3,600 RPM, respectively.
Changes made to default settings are stored and available
for viewing in the quick menu along with any
programming entered into parameters.
1.
Press [Quick Menu].
2.
Scroll to
Q5 Changes Made
and press [OK].
130BB849.10
Q1 My Personal Menu
Q2 Quick Setup
Q5 Changes Made
Q6 Loggings
25.9% 0.00A 1(1)
Quick Menus
Figure 5.12
Q5 Changes Made
About Adjustable Frequency ...
VLT
®
AutomationDrive Instruction
Manual
MG33AM22 - VLT
®
is a registered Danfoss trademark
5-3
5
5
Содержание FC 300
Страница 1: ...MAKING MODERN LIVING POSSIBLE Instruction Manual VLT AutomationDrive FC 300 0 25 75 kW ...
Страница 2: ......
Страница 8: ...Contents VLT AutomationDrive Instruction Manual MG33AM22 VLT is a registered Danfoss trademark ...
Страница 14: ...Introduction VLT AutomationDrive Instruction Manual 1 6 MG33AM22 VLT is a registered Danfoss trademark 1 1 ...
Страница 62: ...Status Messages VLT AutomationDrive Instruction Manual 7 4 MG33AM22 VLT is a registered Danfoss trademark 7 7 ...
Страница 109: ...Index VLT AutomationDrive Instruction Manual MG33AM22 VLT is a registered Danfoss trademark 12 5 ...
Страница 110: ...www danfoss com drives MG33AM22 130R0300 MG33AM22 Rev 2013 03 12 ...