UL Compliance
Fuses or Circuit Breakers must comply with NEC 2009.
Danfoss recommends using a selection of the following
The fuses below are suitable for use on a circuit capable of
delivering 100,000 Arms (symmetrical), 240 V, or 480 V, or
500 V, or 600 V depending on the adjustable frequency
drive voltage rating. With the proper fusing, the drive
Short Circuit Current Rating (SCCR) is 100,000 Arms.
Recommended max. fuse
Power
[kW]
Bussmann
Type RK1
1)
Bussmann
Type J
Bussmann
Type T
Bussmann
Type CC
Bussmann
Type CC
Bussmann
Type CC
0.25–0.37
KTN-R-05
JKS-05
JJN-05
FNQ-R-5
KTK-R-5
LP-CC-5
0.55–1.1
KTN-R-10
JKS-10
JJN-10
FNQ-R-10
KTK-R-10
LP-CC-10
1.5
KTN-R-15
JKS-15
JJN-15
FNQ-R-15
KTK-R-15
LP-CC-15
2.2
KTN-R-20
JKS-20
JJN-20
FNQ-R-20
KTK-R-20
LP-CC-20
3.0
KTN-R-25
JKS-25
JJN-25
FNQ-R-25
KTK-R-25
LP-CC-25
3.7
KTN-R-30
JKS-30
JJN-30
FNQ-R-30
KTK-R-30
LP-CC-30
5.5
KTN-R-50
KS-50
JJN-50
-
-
-
7.5
KTN-R-60
JKS-60
JJN-60
-
-
-
11
KTN-R-80
JKS-80
JJN-80
-
-
-
15–18.5
KTN-R-125
JKS-125
JJN-125
-
-
-
22
KTN-R-150
JKS-150
JJN-150
-
-
-
30
KTN-R-200
JKS-200
JJN-200
-
-
-
37
KTN-R-250
JKS-250
JJN-250
-
-
-
Table 10.18 200–240 V, Frame Sizes A, B and C
Recommended max. fuse
Power
[kW]
SIBA
Type RK1
Littel fuse
Type RK1
Ferraz-
Shawmut
Type CC
Ferraz-
Shawmut
Type RK1
3)
0.25–0.37
5017906-005
KLN-R-05
ATM-R-05
A2K-05-R
0.55–1.1
5017906-010
KLN-R-10
ATM-R-10
A2K-10-R
1.5
5017906-016
KLN-R-15
ATM-R-15
A2K-15-R
2.2
5017906-020
KLN-R-20
ATM-R-20
A2K-20-R
3.0
5017906-025
KLN-R-25
ATM-R-25
A2K-25-R
3.7
5012406-032
KLN-R-30
ATM-R-30
A2K-30-R
5.5
5014006-050
KLN-R-50
-
A2K-50-R
7.5
5014006-063
KLN-R-60
-
A2K-60-R
11
5014006-080
KLN-R-80
-
A2K-80-R
15–18.5
2028220-125
KLN-R-125
-
A2K-125-R
22
2028220-150
KLN-R-150
-
A2K-150-R
30
2028220-200
KLN-R-200
-
A2K-200-R
37
2028220-250
KLN-R-250
-
A2K-250-R
Table 10.19 200–240 V, Frame Sizes A, B and C
Specifications
VLT
®
AutomationDrive Instruction
Manual
MG33AM22 - VLT
®
is a registered Danfoss trademark
10-23
10
10
Содержание FC 300
Страница 1: ...MAKING MODERN LIVING POSSIBLE Instruction Manual VLT AutomationDrive FC 300 0 25 75 kW ...
Страница 2: ......
Страница 8: ...Contents VLT AutomationDrive Instruction Manual MG33AM22 VLT is a registered Danfoss trademark ...
Страница 14: ...Introduction VLT AutomationDrive Instruction Manual 1 6 MG33AM22 VLT is a registered Danfoss trademark 1 1 ...
Страница 62: ...Status Messages VLT AutomationDrive Instruction Manual 7 4 MG33AM22 VLT is a registered Danfoss trademark 7 7 ...
Страница 109: ...Index VLT AutomationDrive Instruction Manual MG33AM22 VLT is a registered Danfoss trademark 12 5 ...
Страница 110: ...www danfoss com drives MG33AM22 130R0300 MG33AM22 Rev 2013 03 12 ...