Enclosure
size
Power (hp [kW])
Recommended
fuse size
Recommended
Max. fuse
Recommended circuit
breaker
Moeller
Max trip level [A]
A1
0.34–2 [0.25–1.5]
gG-10
gG-25
PKZM0-16
16
A2
0.34–3 [0.25–2.2]
gG-10 (0.25–1.5)
gG-16 (2.2)
gG-25
PKZM0-25
25
A3
4–5 [3.0–3.7]
gG-16 (3)
gG-20 (3.7)
gG-32
PKZM0-25
25
B3
7.5 [5.5]
gG-25
gG-63
PKZM4-50
50
B4
10–20 [7.5–15]
gG-32 (7.5)
gG-50 (11)
gG-63 (15)
gG-125
NZMB1-A100
100
C3
25–30 [18.5–22]
gG-80 (18.5)
aR-125 (22)
gG-150 (18.5)
aR-160 (22)
NZMB2-A200
150
C4
40–50 [30–37]
aR-160 (30)
aR-200 (37)
aR-200 (30)
aR-250 (37)
NZMB2-A250
250
A4
0.34–3 [0.25–2.2]
gG-10 (0.34-2) [0.25-1.5]
gG-16 (3) [2.2]
gG-32
PKZM0-25
25
A5
0.34–5 [0.25–3.7]
gG-10 (0.34-2) [0.25-1.5]
gG-16 (3-4) [2.2-3]
gG-20 (5) [3.7]
gG-32
PKZM0-25
25
B1
7.5–10 [5.5–7.5]
gG-25 (7.5) [5.5]
gG-32 (10) [7.5]
gG-80
PKZM4-63
63
B2
15 [11]
gG-50
gG-100
NZMB1-A100
100
C1
20–30 [15–22]
gG-63 (20) [15]
gG-80 (25) [18.5]
gG-100 (30) [22]
gG-160 (20-25) [15-18.5]
aR-160 (30) [22]
NZMB2-A200
160
C2
40–50 [30–37]
aR-160 (40) [30]
aR-200 (50) [37]
aR-200 (40) [30]
aR-250 (50) [37]
NZMB2-A250
250
Table 10.14 200–240 V, Frame Sizes A, B and C
Specifications
VLT
®
AutomationDrive Instruction
Manual
10-20
MG33AM22 - VLT
®
is a registered Danfoss trademark
10
10
Содержание FC 300
Страница 1: ...MAKING MODERN LIVING POSSIBLE Instruction Manual VLT AutomationDrive FC 300 0 25 75 kW ...
Страница 2: ......
Страница 8: ...Contents VLT AutomationDrive Instruction Manual MG33AM22 VLT is a registered Danfoss trademark ...
Страница 14: ...Introduction VLT AutomationDrive Instruction Manual 1 6 MG33AM22 VLT is a registered Danfoss trademark 1 1 ...
Страница 62: ...Status Messages VLT AutomationDrive Instruction Manual 7 4 MG33AM22 VLT is a registered Danfoss trademark 7 7 ...
Страница 109: ...Index VLT AutomationDrive Instruction Manual MG33AM22 VLT is a registered Danfoss trademark 12 5 ...
Страница 110: ...www danfoss com drives MG33AM22 130R0300 MG33AM22 Rev 2013 03 12 ...