Enclosure
size
Power [kW]
Recommended
fuse size
Recommended
Max. fuse
Recommended circuit
breaker Moeller
Max trip level [A]
A1
0.37–1.5
gG-10
gG-25
PKZM0-16
16
A2
0.37–4.0
gG-10 (0.37–3)
gG-16 (4)
gG-25
PKZM0-25
25
A3
5.5–7.5
gG-16
gG-32
PKZM0-25
25
B3
11–15
gG-40
gG-63
PKZM4-50
50
B4
18.5–30
gG-50 (18.5)
gG-63 (22)
gG-80 (30)
gG-125
NZMB1-A100
100
C3
37–45
gG-100 (37)
gG-160 (45)
gG-150 (37)
gG-160 (45)
NZMB2-A200
150
C4
55–75
aR-200 (55)
aR-250 (75)
aR-250
NZMB2-A250
250
A4
0.37–4
gG-10 (0.37–3)
gG-16 (4)
gG-32
PKZM0-25
25
A5
0.37–7.5
gG-10 (0.37–3)
gG-16 (4–7.5)
gG-32
PKZM0-25
25
B1
11–15
gG-40
gG-80
PKZM4-63
63
B2
18.5–22
gG-50 (18.5)
gG-63 (22)
gG-100
NZMB1-A100
100
C1
30–45
gG-80 (30)
gG-100 (37)
gG-160 (45)
gG-160
NZMB2-A200
160
C2
55–75
aR-200 (55)
aR-250 (75)
aR-250
NZMB2-A250
250
Table 10.15 380–500 V, Frame Sizes A, B and C
Specifications
VLT
®
AutomationDrive Instruction
Manual
MG33AM22 - VLT
®
is a registered Danfoss trademark
10-21
10
10
Содержание FC 300
Страница 1: ...MAKING MODERN LIVING POSSIBLE Instruction Manual VLT AutomationDrive FC 300 0 25 75 kW ...
Страница 2: ......
Страница 8: ...Contents VLT AutomationDrive Instruction Manual MG33AM22 VLT is a registered Danfoss trademark ...
Страница 14: ...Introduction VLT AutomationDrive Instruction Manual 1 6 MG33AM22 VLT is a registered Danfoss trademark 1 1 ...
Страница 62: ...Status Messages VLT AutomationDrive Instruction Manual 7 4 MG33AM22 VLT is a registered Danfoss trademark 7 7 ...
Страница 109: ...Index VLT AutomationDrive Instruction Manual MG33AM22 VLT is a registered Danfoss trademark 12 5 ...
Страница 110: ...www danfoss com drives MG33AM22 130R0300 MG33AM22 Rev 2013 03 12 ...