![Visonic PowerMaster-10 G2 Скачать руководство пользователя страница 39](http://html.mh-extra.com/html/visonic/powermaster-10-g2/powermaster-10-g2_quick-user-manual_1032851039.webp)
5. PROGRAMMING
D-304762 PowerMaster-10/30 G2 Installer's Guide
39
Option
Configuration Instructions
premises and activating an "Entry Delay" zone. To answer this requirement, the PowerMaster
provides you with the following configurable options to disarm the system:
A:
At "
any time
" (default), the system can be disarmed at all times from all devices.
B:
During entry delay, the system can be disarmed only using keyfob or prox operated
devices ("
on entry wrless
"
)
.
C:
During entry delay by code, the system can be disarmed only using PowerMaster panel
keypad ("
entry + away kp.
").
D:
During entry delay, the system can be disarmed using keyfobs or by code using the
PowerMaster panel keypad ("
on entry all.
").
Note:
In some PowerMaster variants, this menu is displayed in the Operation Mode only (see
section 5.15).
09:ARMING KEY
Determine that, when activated, the Arming Key will arm AWAY or HOME.
Options:
arm AWAY
(default) and
arm HOME
.
Note:
Arming Key not to be enabled in UL Listed product.
5.5.3 Configuring Zones Functionality
The following table provides you with a detailed description of each option and its configuration settings. To select an
option and change its configuration – refer to section 5.5.1.
Option
Configuration Instructions
21:SWINGER STOP
Define the number of times a zone is allowed to initiate an alarm within a single
arming/disarming period (including tamper & power failure events of detectors, etc.). If the
number of alarms from a specific zone exceeds the programmed number, the control panel
automatically bypasses the zone to prevent recurrent siren noise and excessive reporting to
the Monitoring Station. The zone will be reactivated upon disarming, or 48 hours after having
been bypassed (if the system remains armed).
Options:
after 1 alarm
(default);
after 2 alarms
(default in USA);
after 3 alarms
and
no stop
.
Notes:
1. CP-01 was tested and certified by ETL/Intertek.
2. CP-01 features not to be enabled in UL Listed product.
3. If swinger stop is enabled, a soak
1
fail event will not be triggered.
4. When a detector is in Soak Test
1
mode and also set to bypass, Swinger Stop will
not prevent the sending of events. This may result in excessive reporting of Soak
Fail events.
22:CROSS ZONING
Define whether cross zoning will be active "
ON
" or inactive "
OFF
" (default). Cross zoning is a
method used to counteract false alarms - an alarm will be initiated only when two adjacent
zones (zone couples) are violated within a 30-second time window.
This feature is active only when the system is armed AWAY and only with respect to the
following zone couples: 18+19, 20+21, 22+23, 24+25, 26+27 in PowerMaster-10 G2 system /
40+41, 42+43, 44+45, 46+47, 48+49, 50+51, 52+53, 54+55, 56+57, 58+59, 60+61, 62+63 in
PowerMaster-30 G2 system.
Notes:
1. If one of the two crossed zones is bypassed (see Section 5.5.2), the remaining
zone will function independently.
2. It is recommended that crossed zones will be only zones used for detection of
burglary i.e. "Zone Types": Entry/ Exit, Interior, Perimeter and Perimeter follower.
3. CP-01 was tested and certified by ETL/Intertek.
4. CP-01 features not to be enabled in UL Listed product.
5. If a cross zone is in Soak Test mode
1
, then each zone of this zone couple
functions independently.
Important!
Do not define "cross zoning" to any other zone types such as Fire,
Emergency, 24h audible, 24h silent etc.
1
Soak Test is not applicable for UL installations.