SPIRIT G XL 1-3 KVA - PF0.9 - UPS
www.visionups.com
34
TABLE 20 – Internal charger
UPS type
Model
Remark
Standard unit
1KVAS
Internal charger of 1.4A, 2/3 pieces of 9Ah batteries
1.5KVAS
Internal charger of 1.4A, 3 pieces of 9Ah batteries
2KVAS
Internal charger of 1.4A, 4/6 pieces of 9Ah batteries
3KVAS
Internal charger of 1.4A, 6 pieces of 9Ah batteries
Long backup
unit
1KVAH
Internal charger of 6/12A, external 24/34V battery
1.5KVAH
Internal charger of 6/12A, external 36V battery
2KVAH
Internal charger of 6/12A, external 48/72V battery
3KVAH
Internal charger of 6/12A, external 72/96V battery
TABLE 21 – Battery runtimes at 100% load
(in minutes) (all models)
Model
Internal
batteries
+ 1 EBP
+ 2 EBPs
+ 3 EBPs
+ 4 EBPs
1KVAS (24Vdc)
3
15
25
40
53
1KVAS (36Vdc)
5
25
45
65
85
1.5KVAS (36Vdc)
3
15
25
40
53
2KVAS (48Vdc)
3
15
25
40
53
2KVAS (72vdc)
5
25
45
65
85
3KVAS (72Vdc)
3
17
31
52
69
NOTE: The battery runtimes are approximate and vary depending on the load configuration and battery charge.
TABLE 22 – Battery
Internal battery
EBPs
Battery configuration
1KVA : 24Vdc (2, 12V, 9Ah)
1KVA –EBP : 24Vdc (2 x 2, 12V, 9Ah)
1/1.5KVA : 36Vdc (3, 12V, 9Ah)
1.5KVA –EBP : 36Vdc (2 x 3, 12V, 9Ah)
2KVA : 48Vdc (4, 12V, 9Ah)
2KVA –EBP : 48Vdc (2 x 4, 12V, 9Ah)
2/3KVA : 72Vdc (6, 12V, 9Ah)
3KVA –EBP : 72Vdc (2 x 6, 12V, 9Ah)
Fuses
(2) 30A/250Vdc fuses
(4) 30A/250Vdc fuses per EBP
Type
Sealed, maintenance-free, valve-regulated, lead-acid, with minimum 3-year float service life
at 25°C
Monitoring
Advanced monitoring for earlier failure detection and warning
Recharge time (to 90%)
8 hours to 90%
Battery port
External six-pole «Anderson» connector on UPS for connection to EBP