SPIRIT G XL 1-3 KVA - PF0.9 - UPS
www.visionups.com
21
④ Exit the setting interface. Press and hold the function setting key
longer
than ½ second (shorter than 2 seconds), exit the setting interface and return to
main interface.
If set as used, the corresponding word is «ON». Check the battery connections
monthly.
Warning
code display
setting
① Enter the setting interface. Press and hold the function setting key
longer
than 2 seconds to reach the setting interface. Press and hold the scroll key
longer than ½ second (shorter than 2 seconds), select the function setting, choose
the setting interface of the warning code display. The letters «wc» flash.
② Enter the «wc» setting interface. Press and hold the function setting key
longer than ½ second (shorter than 2 seconds). Reach then the setting interface of
«wc». The letters «wc» light for a long time. The «ON» (or «OFF») below «wc» will
flash. Press and hold the scroll key
longer than ½ second (shorter than 2
seconds) to determine the «wc» function as used or unused. If used, the
corresponding word is «ON», if unused the corresponding word is «OFF». It can
be determined by yourself.
③ Confirm the «wc» setting interface. After selection of «ON» or «OFF», press
and hold the function setting key
longer than ½ second (shorter than 2
seconds). Now, the «wc» setting function is completed and the «ON» or «OFF»
below «wc» lights without flashing.
④ Exit the setting interface. Press and hold the function setting key
longer
than ½ second (shorter than 2 seconds), exit the setting interface and return to
main interface.
If set as used, the corresponding word is «ON», 2-5 seconds cycle warning code.
For the warning codes information, please refer to table 24.
EPO input
polarity
setting
① Enter the setting interface. Press and hold the function setting key
longer
than 2 seconds to reach the setting interface. Press and hold the scroll key
longer than ½ second (shorter than 2 seconds), select the function setting, choose
the setting interface of EPO input polarity. The letters «EPO» flash.
② Enter the EPO input polarity setting interface. Press and hold the function
setting key
longer than ½ second (shorter than 2 seconds). The letters «EPO»
stop flashing. The letters below «EPO» will flash. Press and hold the scroll key
longer than ½ second (shorter than 2 seconds), select the EPO input polarity, «+P»
(open circuit executes the EPO function) or «-P» (short circuit executes the EPO
function).
③ Confirm the setting. After selection of the EPO input polarity, press and hold
the function setting key
longer than ½ second (shorter than 2 seconds). The
setting is completed now.
④ Exit the setting interface. Press and hold the function setting key
longer
than ½ second (shorter than 2 seconds), exit the setting interface and return to
main interface.
(Battery)
End of
discharge
setting
① Enter the setting interface. Press and hold the function setting key
longer
than 2 seconds to reach the setting interface. Press and hold the scroll key
longer than ½ second (shorter than 2 seconds), select the «Eod» setting. The
letters «Eod» will flash.
② Enter the «Eod» setting interface. Press and hold the function setting key
longer than ½ second (shorter than 2 seconds). Now, the letters «Eod» will stop
flashing.
③ Set the «Eod» tolerance range. Press and hold the scroll key
or
longer
than ½ second (shorter than 2 seconds) to select the voltage range in %. 10.0V,
10.5V, 11.0V (default is 10.0V). Press and hold the function setting key
longer
than ½ second (shorter than 2 seconds) to confirm the selection.