SPIRIT G XL 1-3 KVA - PF0.9 - UPS
www.visionups.com
24
TABLE 8 – Battery number configuration
All UPS and EBP cabinets
Number of battery strings
UPS only (internal batteries)
1 (by default)
UPS + 1EBP
3
UPS + 2EBPs
5
UPS + 3EBPs
7
UPS + 4EBPs
9
NOTE:
The UPS contains one battery string. Each EBP contains two battery strings.
WARNINGS:
The following process must be performed, if the UPS is connected with a generator:
First turn on the generator. As soon as its runs stable, connect the output power of the generator to the UPS input
terminal. Then turn on the UPS. After the UPS is powered on, please turn on the loads one by one.
It is recommended that the generator capacity is twice as high as the UPS power range.
Prefer to not use the ECO mode if the quality of input AC mains is not good.