• This manual provides important safety-related information. Thoroughly read and understand 

this manual before installing and using the product. 

• Keep this manual in a convenient location so that you can refer to it whenever necessary.
• The contents of this manual are subject to change without notice.

BY35S/BY50S

BY80S/BY120S

Uninterruptible Power Supply

Instruction Manual

Содержание Powli BY120S

Страница 1: ...stand this manual before installing and using the product Keep this manual in a convenient location so that you can refer to it whenever necessary The contents of this manual are subject to change wit...

Страница 2: ...considerations related to operation maintenance and management must be taken such as duplicating the system and emergency power generation facilities Observe the contents of this manual such as the us...

Страница 3: ...wed when using the UPS and batteries 2 SYMBOL Power output ON OFF switch 3 INTERNAL BATTERY Internal battery voltage is 12V DC FOR BY35S BY50S BY80S BY120S 4 TEMPERATURE RATING The maximum ambient tem...

Страница 4: ...tents Page 1 Perform installation and connection Page 6 Check the operation and displays Pages 12 Charge the battery Page 13 Measure the backup time Page 28 Read Using the UPS monitoring software Page...

Страница 5: ...p procedures and basic operation 17 3 3 Interpreting beeps and displays 20 4 UPS functions 22 4 1 Suspending a beep 22 4 2 Self diagnosis test 22 4 3 Description of the auto battery test function 23 4...

Страница 6: ...lications with the same level of importance Warning Important information for safe operation is described Be sure to read it before installation and start of use Misuse may cause injury or property da...

Страница 7: ...or environmental conditions during use storage Do not install or store the unit in the places listed below Do not store in places where the humidity is lower than 10 or higher than 90 Do not use the u...

Страница 8: ...ower supply output receptacles Accumulated dust may cause a fire Do not use the unit in a closed place and do not cover the unit Doing so may cause abnormal heating or a fire If you notice abnormal so...

Страница 9: ...t doing so could cause injury or burns due to liquid acid leakage Use a specified battery for replacement Not doing so may cause a fire Product model BYB50S for BY35S BY50S BYB80S for BY80S and BYB120...

Страница 10: ...the unit The unit repeatedly and frequently switches between Commercial Power Mode and Battery Mode which may shorten the life of the battery The page printer has a large peak current so an excess of...

Страница 11: ...months the internal timer is reset and the scheduled operation does not start Note that this period reduces to approximately half when the battery is dead If a period of 3 months is exceeded you start...

Страница 12: ...age contents are included and there is no damage found on their appear ance If you should notice defects or anything wrong contact us ____ BY35S BY50S BY80S BY120S Instruction manual Japanese and Engl...

Страница 13: ...1 3 Name of each part B C D BY35S BY50S BY80S BY120S A Status indicator digital display B Battery replacement lamp C Beep stop test switch D Power switch A Status indicator digital display B Battery r...

Страница 14: ...BY35S BY50S BY80S BY120S 1 3 Bottom view BY35S BY50S A Fixation screw for battery replacement cover B Battery replacement cover A B...

Страница 15: ...cable E Power supply output receptacles A USB connector B Setting switch C AC input overcurrent protection switch D AC input cable E Power supply output receptacles A USB connector B Setting switch C...

Страница 16: ...BY35S BY50S BY80S BY120S 1 5 1 4 Explanation of symbols used on unit Symbol Description Power output ON OFF switch Suspend a beep Batteries at end of useful life necessary to replace the batteries...

Страница 17: ...ct devices such as dryers some solenoid valves etc which have a half wave rectifier that allows only half cycle AC power to flow through Overcurrent may damage the UPS Connect the unit to a wall outle...

Страница 18: ...ng of the plug strip heats up which may cause a fire Do not pinch or tie the cable of the unit Doing so may cause the cable to be damaged or heated which may cause an electric shock or a fire If the c...

Страница 19: ...ect a page printer such as a laser printer to the unit The unit repeatedly and frequently switches between Commercial Power Mode and Battery Mode which may shorten the life of the battery The page pri...

Страница 20: ...contacting us about the device Check the unit s serial number inscribed on the back of the unit or printed on the attached serial number label Correct Positions BY35S BY50S BY80S BY120S Incorrect Pos...

Страница 21: ...4 Maximum screw length 12 mm Maximum tightening torque 1 57 N m Proper Positions Horizontal Vertical Attach the unit to the base plate by threading 4 screws through the temporary screw holes on the un...

Страница 22: ...commercial power Router or other peripheral PC Example of connection 1 Example of connection 2 A 2 pin input plug of a connecting device can be connected to the power supply output receptacle whithou...

Страница 23: ...rom commercial power Status indicator Description Power switch ON Operating normally 2 Bring all the connected devices into operation Including devices connected to the AC outlet of your PC Operate th...

Страница 24: ...o 4 on page 12 If the problem persists after checking the 2 points above contact us ____ See also Setting switch 1 can be used to turn the beeper ON OFF Page 24 6 Connect the AC input plug to a wall o...

Страница 25: ...rging the battery 2 7 Recharging the battery 2 6 Measuring the initial value of backup time When you measure the backup time initial value of the unit in your environment this value can be used as a g...

Страница 26: ...plug from a wall outlet commercial power Using the unit under such conditions may cause a fire If the unit becomes wet immediately stop using it unplug the AC input cable and contact us at __________...

Страница 27: ...ect whether or not auto restart is performed See Page 24 Scheduled operation using the UPS monitoring software When performing scheduled operation in which the UPS is stopped and a device such as a br...

Страница 28: ...setting Input power sensitivity setting page 25 The status indicator displays and the self diagnostic test is performed in Battery Mode for about 10 seconds If the battery voltage is low the self dia...

Страница 29: ...ing switch 1 can be used to turn the beeper ON OFF Page 24 indicates blinking Status indicator Battery replacement Beep Output Charging Description Solution Intermittent 4 second intervals ON OFF Disc...

Страница 30: ...te ly and power output is stopped the UPS restarts automatically and resumes power output The expended battery begins to charge See also Setting switch 2 can be used to select whether or not auto rest...

Страница 31: ...de due to power failure or AC input error Output will stop if Battery Mode continues Same as above Battery level is low so output will soon stop Battery is dead so output stopped This is displayed onl...

Страница 32: ...ve Output stopped due to an internal communication error Continuous 27 Same as above Output stopped due to battery charge voltage error under Output stopped due to problem with the internal temperatur...

Страница 33: ...tatus indicator No beep sounds After about 10 seconds when the test is complete the normal operation automatically starts 3 If the status indicator battery replacement lamp blinks and the beeper sound...

Страница 34: ...cribed in 4 Displays and beeps when there is an equipment failure and 5 Display and beep for battery replacement ON DIP 1 2 5 6 7 8 3 4 Setting switch ON ON side OFF side 1 Selecting functions with th...

Страница 35: ...t automatically starts and begins to output when the commercial power is restored ON Does not automatically start when power is restored After the unit is shut down with the UPS monitoring software it...

Страница 36: ...re quency the last time there was AC input When using the cold start function When performing operation with cold start a second time turn OFF the power switch and wait at least 20 seconds before turn...

Страница 37: ...d OFF the setting mode quits and the unit enters power switch OFF status status 2 2 Settings ON Cold start ON mode C 1 C D D D A B OFF Cold start OFF mode Factory shipped setting C 1 C D D D 1 Display...

Страница 38: ...ble 1 Complete beep stop 2 Output voltage setting 3 Voltage sensitivity mode setting 4 Cold start setting 5 Maximum backup time setting 6 Automatic self diagnostic testing 7 Startup delay time setting...

Страница 39: ...e value in the right table for conversion When the power factor is unknown enter 1 The power factor usually ranges between 0 6 and 1 Indica tion Value VA power factor W A power factor 100 W 1 When the...

Страница 40: ...rence only Times may vary according to battery life and external environmental conditions temperature etc Power consumption of connected devices W Minutes Backup time BY120S BY80S BY35S BY50S 140 120...

Страница 41: ...hen you mea sured the initial value to make judgment accurately When maintaining the connected equipment turn OFF the power switch and disconnect the AC input plug Even if you disconnect the AC input...

Страница 42: ...battery may explode or leak dilute sulfuric acid Do not use a new battery and an old battery at the same time Dilute sulfuric acid may leak The battery can be replaced while the unit is stopped power...

Страница 43: ...e the top Remove the one fixation screw one of the battery replacement cover using a screwdriver turn counter clockwise 2 Slide the battery replacement cover upward to remove the cover Battery recycli...

Страница 44: ...ry by the left hand holding the battery by the right hand If it is hard to remove move the connector up and down with your fingers or long nose pliers to pull out Pull out the battery cable black from...

Страница 45: ...il they click Hold the battery by the right hand and insert the connector of the battery cable red into the terminal by the left hand Hold the battery by the right hand and insert the connector of the...

Страница 46: ...a wall outlet commercial power and turn ON the power switch of the UPS When operation starts the self diagnostic test is automatically performed Nor mal operation resumes after the 10 second test Aft...

Страница 47: ...remove the 2 screws Detach the front panel Pull the front panel upward a little if the front panel is hard to detach 2 Disconnect the battery connector and remove the metal cover Remove the red and b...

Страница 48: ...t the new battery pack You may hear a pop sound when you connect the battery if it is replaced after the unit s operation is stopped but this is not abnormal Fit the metal cover into the grooves and s...

Страница 49: ...attery when operation was stopped Connect the AC input plug to a wall outlet commercial power and turn ON the power switch of the UPS When operation starts the self diagnostic test is automatically pe...

Страница 50: ...cause deformation or discoloration 2 Removing dust from the AC input plug power supply output receptacles of the UPS Stop all the connected devices and the UPS and disconnect the AC input plug from a...

Страница 51: ...munication method UPS monitoring software Reference BY35S BY50S BY80S BY120S Windows 7 Windows Vista Windows Server 2008 including R2 Windows Server 2003 including R2 x64 Edition Windows XP x64 Editio...

Страница 52: ...PowerAct Pro 4 x Compatible OS Windows 7 Windows Vista Windows Server 2008 including R2 Windows Server 2003 including R2 x64 Edition Windows XP x64 Edition Windows Server 2003 including R2 Windows XP...

Страница 53: ...at shutdown items such as application programs can be launched 10 Event log save Information of events that occur on the UPS power supply problems setting changes occurrences of failure etc are saved...

Страница 54: ...8 For more information and operation refer to the Quick Installation Guide for UPS Monitoring Software and the online help in the included CD ROM 7 1 When using the included UPS monitoring software to...

Страница 55: ...the UPS monitoring software To manually start up this unit after it has been stopped by a scheduled operation turn OFF the power switch and turn it back ON again To stop the unit when it is in operat...

Страница 56: ...he included UPS service driver on the computer Software to install UPS service driver How to install Refer to the separate UPS monitoring software installation guide USB USB BY35S BY50S BY80S BY120S I...

Страница 57: ...nt that consumes large power This problem may occur also when you connect many devices to a plug strip or extension cord connected to the UPS if it is a long or thin cable Does not turn ON when power...

Страница 58: ...ine wave sine wave Waveform distortion rate In Battery Mode 25 or less Output receptacle NEMA 5 15R x 4 receptacles Switching time 10 msec max Battery Backup time 2 6 min or more 3 5 min or more 4 min...

Страница 59: ...8 B Dimensions BY35S BY50S 165 0 5 92 1 285 1 Unit mm Dimensions are not including the height of the rubber feet The height of the rubber feet is about 0 8 mm and the height including the rubber feet...

Страница 60: ...50S BY80S BY120S 49 BY80S Unit mm Dimensions are not including the height of the rubber feet The height of the rubber feet is about 1 6 mm and the height including the rubber feet is 236 6 mm 235 1 85...

Страница 61: ...erences 50 BY120S Unit mm 328 5 1 90 1 298 1 Dimensions are not including the height of the rubber feet The height of the rubber feet is about 1 6 mm and the height including the rubber feet is 299 6...

Страница 62: ...uct Models BY35S BY50S BY80S BY120S Replacement battery pack BYB50S BYB80S BYB120S Bracket BYP50S BYP80S Charging circuit 100 VAC input AC input overcurrent protection DC DC converter Battery Inverter...

Страница 63: ...No part or whole of this manual may be reproduced without permission The contents of this manual are subject to change without notice OMRON Corporation K1L D 09007C 9475019 3B...