Notes: 1) The addition of chlorine (bleach) to a hot water tank that has in the past been fed with untreated raw water with 

high levels of other contaminants (iron, manganese, hydrogen sulphide, organics, etc.) will result in oxidation 
of these contaminants and may require repeated flushing of the hot water tank. This contingency must be dealt 
with independently under the start-up procedure for any other conditioners that may form a part of the 
pre-treatment for the UV unit.

2) The above disinfection procedure will result in a massive chlorine residual far in excess of the 0.5 to 1.0 mg/L 

typically present in municipally chlorinated water and of a magnitude consistent with the minimum 50 mg/L 
chlorine solution recommended for the disinfection of distribution systems known to be contaminated. Do not 
consume water until complete system has been flushed

.

3) As the monitored systems include a 254nm UV intensity monitor, note that the introduction of the bleach 

solution required for disinfection will trigger a temporary low UV condition. This is due to the fact that the bleach 
physically “clouds” the raw water. Once the bleach runs through the system, the alarm condition will return to 
normal. During this sanitization process, the audible alarm condition on the controller can be temporarily 
deferred by pressing the “RESET” switch for 5 seconds. By doing this, the audible alarm will be silenced. The 
system will display 

 

on the controller LED. This condition will remain for 12 hours unless the system is 

manually reset as outlined on page 10 of this manual.

Section 4

Maintenance

4.1 Replacing UV Lamp

Lamp replacement is a quick and simple procedure requiring no special tools. The UV lamp must be replaced after 9000 
hours of continuous operation (approximately one year) in order to ensure adequate disinfection.

W A R N I N G

  •

Always disconnect power before performing any work on the disinfection system.

  •

Always shut-off water flow and release water pressure before servicing.

  •

Regularly inspect your disinfection system to ensure that the power indicators are on and no alarms are present.

  •

Replace the UV lamp annually (or biennially if seasonal home use) to ensure maximum disinfection.

  •

Always drain the chamber when closing a seasonal home or leaving the unit in an area subject to freezing temperatures.

N O T I C E

  •

Reset lamp life timer after lamp replacement. Refer to 

Section 5.1.3

. Refer to 

www.lamprecycle.org

 for lamp disposal.

  •

Do not use water during replacement of UV lamp.

5

2

1

2

2

2

•   

Re-install the housings.

•   

Turn on the cold water supply.

•   

Open each faucet and all 
water openings until you 
smell the bleach and then 
close the faucets.

6

2

1

2

2

2

•   

Turn on the hot water supply.

•   

Open each faucet and all 
water openings until you smell 
the bleach and then close the 
faucets.

7

1

0

30

15

45

30 mins

2

•   

DO NOT use water for 30 
minutes.

•   

Flush the system until no 
chlorine smell is detectable 
and reinstall the filters.

8

•   

Reinstall filter cartridge(s).

Installation

Mantenimiento

4.3 Limpieza y reposición del sensor UV

Los sedimentos y depósitos minerales pueden acumularse en la ventana del sensor y reducir la cantidad de energía UV 
detectada. Con un buen mantenimiento del equipo de tratamiento previo se reduce la acumulación de residuos. Si el 
sistema indica una baja intensidad de UV, podría deberse a manchas en la ventana del sensor o en la vaina tubular 

de cuarzo.

Requisitos previos:

Quite y limpie la vaina tubular de cuarzo.

Nota: La 

vaina tubular de cuarzo y el sensor UV deben limpiarse al mismo tiempo.

Procedimiento:

A D V E R T E N C I A

El sensor UV es un instrumento muy delicado. Debe ir con mucho cuidado a la hora de manipularlo y limpiarlo. La propia ventana del sensor está hecha de un 
cuarzo muy frágil, por lo que debe tener cuidado de no agrietarla o romperla. La garantía del fabricante no cubre los daños debidos a la negligencia o a usos 
indebidos.

1

•   

Desconecte el sensor UV del 

controlador desconectando el 
cable del sensor.

2

•   

Retire el sensor UV y la junta tórica 

agarrando el cuerpo del sensor 

y girándolo en el sentido contrario 
a las agujas del reloj.

Commercial 
     Scale
   Remover

3

0

30

15

45

30 mins

•   

Solo debe sumergir el extremo del 

sensor en el desincrustante 
durante 30 minutos.

4

1

2

•   

Limpie el sensor con un bastoncillo 

de algodón y rocíelo con agua.

•   

Vuelva a introducir el sensor UV 

junto con la junta tórica hasta que 
la junta sea impermeable.

Содержание VH200

Страница 1: ...f 1 519 763 5069 Courriel info viqua com www viqua com 425 Clair Rd W Guelph Ontario Canadá N1L 1R1 t 1 519 763 1032 f 1 800 265 7246 solo EE UU y Canadá t 31 73 747 0144 solo Europa f 1 519 763 5069 correo electrónico info viqua com www viqua com 425 Clair Rd W Guelph Ontario Canada N1L 1R1 t 1 519 763 1032 f 1 800 265 7246 US and Canada only t 31 73 747 0144 Europe only f 1 519 763 5069 e mail i...

Страница 2: ...reclamación bajo garantía necesitará su factura original o bien deberá haber completado y enviado su tarjeta de registro de producto por correo postal o en línea Cobertura específica de la garantía La cobertura de la garantía es específica de la gama de productos de VIQUA La cobertura de la garantía está sujeta a las condiciones y limitaciones establecidas en la sección Condiciones y limitaciones ...

Страница 3: ...l if you are in doubt as to whether the outlet is properly grounded DO NOT modify the plug provided with this system if it does not fit in the outlet have a proper outlet installed by a qualified electrician DO NOT use any type of adapter with this system GROUND FAULT CIRCUIT INTERRUPTER PROTECTION To comply with the National Electrical Code NFPA 70 and to provide additional protection from the ri...

Страница 4: ...r yank cord to pull plug from outlet Always grasp the plug and pull to disconnect SYSTEM PROTECTION To protect your Controller a UL1449 certified or equivalent transient voltage surge suppressor is strongly recommended The UV lamp in this system conforms to the applicable provisions of the Code of Federal Regulations CFR requirements including Title 21 Chapter 1 Subchapter J Radiological Health Re...

Страница 5: ...uales se llene de cloro lejía antes de que el agua salga del sistema UV Para funcionar de manera eficaz el sistema de desinfección debe tener un sistema de distribución libre de bacterias Consultar la Sección 3 2 Posible entrada de sedimentos a través del pre filtro Analice el agua de suministro para descartar la turbiedad es posible que necesite un filtrado escalonado para recoger todos los sedim...

Страница 6: ...fection System Note UV system should be the final piece of treatment equipment Optional flow restrictor Note Mandatory for NSF credited systems Optional water softener To drain Optional by pass assembly Optional by pass assembly Optional by pass assembly Optional solenoid valve Hot water pipes Cold water pipes Customer supplied GFCI circuit to match voltage Water meter Main water shut off 5 Micron...

Страница 7: ...2 segundos durante las condiciones de bajo nivel de UV Nota Niveles de UV de APLAZAMIENTO para aplazar temporalmente la alarma acústica y reactivar la válvula de solenoide si se ha instalado durante una alarma de nivel bajo de UV mantenga pulsado el botón de reinicio del temporizador durante cinco segundos Con esto se silenciará la condición de alarma acústica y se activará la salida de solenoide ...

Страница 8: ... que sustituir la lámpara de 365 días a 1 día Al llegar a 0 días el controlador mostrará y emitirá un chirrido intermitente 1 segundo encendido 5 segundos apagado para indicar la necesidad de cambiar la lámpara 5 1 2 Interpretación del código A3 APLAZAMIENTO cuando aparece en la pantalla LED el mensaje de fin de la vida útil de la lámpara o A3 la alarma acústica se puede aplazar hasta 4 veces sepa...

Страница 9: ...are present Replace the UV lamp annually or biennially if seasonal home use to ensure maximum disinfection Always drain the chamber when closing a seasonal home or leaving the unit in an area subject to freezing temperatures N O T I C E Reset lamp life timer after lamp replacement Refer to Section 5 1 3 Refer to www lamprecycle org for lamp disposal Do not use water during replacement of UV lamp 5...

Страница 10: ...ED display will read once again 10 51 Maintenance Procedimiento Nota Tras reemplazar la lámpara UV o la vaina tubular de cuarzo realice el procedimiento de desinfección y consulte la Sección 3 2 1 Drene la cámara usando el puerto de drenaje 2 1 2 3 Quite la tuerca de retención el muelle flotante y la junta tórica de la parte inferior 3 1 2 Quite la tuerca de retención y la junta tórica de la parte...

Страница 11: ... la vaina tubular de la lámpara Esta capa debe retirarse porque reduce la cantidad de luz UV que llega al agua reduciendo de este modo el rendimiento de la desinfección Si la vaina tubular no puede limpiarse deberá reemplazarse por otra Requisitos previos Cortar el suministro de agua y drenar todas las líneas Quitar la lámpara UV Consulte Sección 4 1 1 Corte la línea de agua de la cámara y libere ...

Страница 12: ...or de intensidad UV de 254 nm tenga en cuenta que la introducción de la solución de lejía requerida para efectuar la desinfección provocará una condición temporal de bajo nivel de UV Esto se debe a que la lejía enturbia físicamente el agua no potable Una vez que la lejía circule por el sistema la condición de alarma volverá al estado normal Durante el proceso de desinfección la condición de alarma...

Страница 13: ...optimum protection against microbiological contamination in water DO NOT disregard the warning signals The best way to ensure optimum UV performance is to have the water microbiologically tested by a recognized testing agency on a regular basis Instalación 5 Instale la lámpara UV Consulte Sección 4 1 6 Cuando se hayan realizado todas las conexiones de tuberías conecte el suministro de agua lentame...

Страница 14: ...tes the UV level is still within a safe level however cleaning or lamp sleeve replacement may soon be required to Indicates the UV level is nearing the point of unsafe UV intensity UV system should be immediately serviced Indicates the UV level has now reached a level that is unsafe At this level the water should not be consumed The system water supply should be examined to determine the reason fo...

Страница 15: ...oque un peligro de incendio Es muy recomendable usar bucles de goteo en los cables conectados al controlador Consulte Figura 5 El sistema de agua completo incluidos los depósitos de presión o agua caliente se deben esterilizar antes de la puesta en marcha Para ello enjuague con cloro lejía doméstica para destruir toda contaminación residual Consulte Sección 3 2 El sistema de desinfección está dise...

Страница 16: ...tem should not be installed on a circuit which is incorporated into a light switch Lamp Failure Alarm on New Lamp Loose connection between lamp and connector Disconnect lamp from connector and reconnect ensuring that a tight fit is accomplished Moisture build up in connector may keep lamp and connector from making a solid connection Eliminate chance of any moisture getting to the connector and or ...

Страница 17: ...l debido la exposición a rayos UV es recomendable usar accesorios metálicos y canalización de cobre de al menos 25 4 cm en la salida de la cámara UV AVISO La lámpara UV en el interior del sistema de desinfección tiene una clasificación nominal con una vida eficaz de aproximadamente 9000 horas Para garantizar una protección continua reemplace la lámpara UV una vez al año Los niños no deben usar el ...

Страница 18: ...surización segura Este símbolo indica que se requiere el uso de botas de seguridad Este símbolo indica que el sistema está bajo presión Este símbolo indica que el operador debe leer toda la documentación disponible para realizar los procedimientos requeridos Este símbolo indica que existe peligro de exposición a rayos UV Se debe usar protección adecuada Este símbolo indica que el fontanero debe us...

Страница 19: ...rcionarle años de funcionamiento sin problemas con un mínimo mantenimiento para proteger su agua potable contra contaminantes microbiológicos Para garantizar la continua desinfección del agua las lámparas UV se deben reemplazar cada año por repuestos VIQUA de fábrica Las lámparas VIQUA son fruto de un extenso desarrollo que ha resultado en una plataforma de desinfección altamente eficaz con un ren...

Страница 20: ...e date of purchase During this time VIQUA will repair or replace at its option any defective parts covered by the warranty Please return the defective part to your dealer who will process your claim One Year Limited Warranty for UV lamps Sleeves and UV Sensors VIQUA warrants UV lamps sleeves and UV sensors to be free from defects in material and workmanship for a period of one 1 year from the date...

Страница 21: ...This page intentionally left blank ...

Страница 22: ...This page intentionally left blank ...

Страница 23: ...This page intentionally left blank ...

Страница 24: ...f 1 519 763 5069 Courriel info viqua com www viqua com 425 Clair Rd W Guelph Ontario Canadá N1L 1R1 t 1 519 763 1032 f 1 800 265 7246 solo EE UU y Canadá t 31 73 747 0144 solo Europa f 1 519 763 5069 correo electrónico info viqua com www viqua com 425 Clair Rd W Guelph Ontario Canada N1L 1R1 t 1 519 763 1032 f 1 800 265 7246 US and Canada only t 31 73 747 0144 Europe only f 1 519 763 5069 e mail i...

Отзывы: