52
Plug
sYS
Terminals
Function
Explanation
212.3
DHW circulation pump
Connection values
■ Output: 50 W
■ Voltage: 230 V~
■ Max. switching current: 4(2) A
212.4
Solar circuit pump with high
limit safety cut-out (max. 95
°C) for DHW cylinders
Connection values
■ Output: 130 W
■ Voltage: 230 V~
■ Max. switching current: 4(2) A
Connect the high limit safety cut-out to
the solar circuit pump
in series
(see high
limit safety cut-out installation instruc-
tions).
Connecting a temperature limiter as a maximum temperature limiter for under-
floor heating
Connecting a general temperature
limiter
B
M
1~
C
B
X2.N
?
A
X1.
Connecting the temperature limiter,
part no. 7151 728, 7151 729
B
M
1~
C
B
sÖ
X2.N
?
A
X1.
Installation sequence
Electrical connection
(cont.)
5623 661 GB
Содержание Vitocal 242-S
Страница 26: ...26 6 8 P301 P501 P303 P302 X25 F23 F6 7 Installation sequence Installing the internal unit cont 5623 661 GB ...
Страница 27: ...27 SLP N 9 11 aCH sG lJ 10 Installation sequence Installing the internal unit cont 5623 661 GB Installation ...
Страница 28: ...28 X20 2x 16 17 2x 12 14 18 13 15 Installation sequence Installing the internal unit cont 5623 661 GB ...
Страница 29: ...29 2x 4x 4x 6x 21 19 20 22 Installation sequence Installing the internal unit cont 5623 661 GB Installation ...
Страница 32: ...32 Installation sequence Installing the internal unit cont 5623 661 GB ...
Страница 95: ...95 Removing cover from programming unit if necessary 5 4 4x Troubleshooting Repairs cont 5623 661 GB Service ...
Страница 110: ...110 0003 0006 0005 0008 0007 0001 0009 0010 0002 0004 Parts lists internal unit Internal unit casing cont 5623 661 GB ...