33
■ The external unit is pre-filled with
refrigerant R410A.
■ Install oil lift bends (see illustration)
into the vertical lines in the following
cases:
– In heating mode, if the internal unit
is installed higher than the external
unit.
– In cooling mode, if the internal unit is
installed lower than the external unit.
Routing refrigerant lines
Vitocal 242-S, type AWT-AC
241.A04
241.A07
241.A10
241.A13
Refrigerant lines
Min. line length
3 m
3 m
3 m
3 m
Max. line length
20 m
30 m
30 m
30 m
Max. height differential internal
unit – external unit
10 m
15 m
15 m
15 m
Note
No topping up is required for line lengths
between 3 and 12 m.
5000
5000
B
C
D
E
A
Example: type AWT-AC 241.A07
A
Internal unit
B
External unit
C
Liquid line
Installation sequence
Connecting refrigerant lines
5623 661 GB
Installation
Содержание Vitocal 242-S
Страница 26: ...26 6 8 P301 P501 P303 P302 X25 F23 F6 7 Installation sequence Installing the internal unit cont 5623 661 GB ...
Страница 27: ...27 SLP N 9 11 aCH sG lJ 10 Installation sequence Installing the internal unit cont 5623 661 GB Installation ...
Страница 28: ...28 X20 2x 16 17 2x 12 14 18 13 15 Installation sequence Installing the internal unit cont 5623 661 GB ...
Страница 29: ...29 2x 4x 4x 6x 21 19 20 22 Installation sequence Installing the internal unit cont 5623 661 GB Installation ...
Страница 32: ...32 Installation sequence Installing the internal unit cont 5623 661 GB ...
Страница 95: ...95 Removing cover from programming unit if necessary 5 4 4x Troubleshooting Repairs cont 5623 661 GB Service ...
Страница 110: ...110 0003 0006 0005 0008 0007 0001 0009 0010 0002 0004 Parts lists internal unit Internal unit casing cont 5623 661 GB ...