72
Evacuating refrigerant lines and internal unit
!
Please note
Commissioning is weather-
dependent.
In the case of high relative humid-
ity or outside temperatures below
0 °C, please observe the follow-
ing:
■ Use nitrogen 5.0 for the pres-
sure test.
■ During evacuation, take suita-
ble steps to keep the surface
temperature of the refrigerant
lines
above
0 °C.
Danger
Direct contact with refrigerant
can cause skin damage.
Wear safety goggles and protec-
tive gloves when working on the
refrigerant circuit.
!
Please note
Before evacuating the refrigerant
lines and the internal unit, check
all connections for tightness with
leak detection spray.
Keep the valves on the external
unit shut, and fill the system with
nitrogen through the service
valve. The test pressure is the
max. permissible operating pres-
sure.
Commissioning, inspection, maintenance
Further details regarding the individual steps
(cont.)
5623 661 GB
Содержание Vitocal 242-S
Страница 26: ...26 6 8 P301 P501 P303 P302 X25 F23 F6 7 Installation sequence Installing the internal unit cont 5623 661 GB ...
Страница 27: ...27 SLP N 9 11 aCH sG lJ 10 Installation sequence Installing the internal unit cont 5623 661 GB Installation ...
Страница 28: ...28 X20 2x 16 17 2x 12 14 18 13 15 Installation sequence Installing the internal unit cont 5623 661 GB ...
Страница 29: ...29 2x 4x 4x 6x 21 19 20 22 Installation sequence Installing the internal unit cont 5623 661 GB Installation ...
Страница 32: ...32 Installation sequence Installing the internal unit cont 5623 661 GB ...
Страница 95: ...95 Removing cover from programming unit if necessary 5 4 4x Troubleshooting Repairs cont 5623 661 GB Service ...
Страница 110: ...110 0003 0006 0005 0008 0007 0001 0009 0010 0002 0004 Parts lists internal unit Internal unit casing cont 5623 661 GB ...