61
Parameter address A5:...
With heating circuit pump logic function: Heating circuit pump "OFF"
1
OT > RT
set
+ 5 K
2
OT > RT
set
+ 4 K
3
OT > RT
set
+ 3 K
4
OT > RT
set
+ 2 K
5
OT > RT
set
+ 1 K
6
OT > RT
set
7
to
OT > RT
set
–
1 K
15
OT > RT
set
–
9 K
Coding in the delivered condition
Possible change
Extended economy function adjusted outside temperature
A6:36
Extended economy mode
not
ac-
tive
A6:5
to
A6:35
Extended economy mode active:
The burner and heating circuit pump
are switched off and the mixer will
be closed at a variable value, adjust-
able between 5 and 35 °C plus 1 °C.
The basis for this is the adjusted
outside temperature. This is derived
from the actual outside temperature
and a time constant that takes ac-
count of the way an average building
cools down.
Extended economy function mixer
A7:0
Without mixer economy function
(only for heating circuits with mix-
er)
A7:1
With mixer economy function (exten-
ded heating circuit pump logic):
Heating circuit pump also "OFF":
■
If the mixer has been trying to
close for more than 20 min.
Heating circuit pump "ON":
■
If the mixer changes to control
function
■
If there is a risk of frost
Pump idle time, transition reduced mode
A9:7
With pump idle time: Heating cir-
cuit pump "OFF" if set value is
modified by changing the operating
mode or changing the set room
temperature
A9:0
Without pump idle time
A9:1
to
A9:15
With pump idle time, adjustable from
1 to 15
Weather-compensated/room temperature hook-up
b0:0
With remote control: Heating
mode/reduced mode: Weather-
compensated (change the code
only for the heating circuit with
mixer)
b0:1
Heating mode: Weather-compensa-
ted
Reduced mode: With room tempera-
ture hook-up
b0:2
Heating mode: With room tempera-
ture hook-up
Reduced mode: Weather-compen-
sated
b0:3
Heating mode/reduced mode: With
room temperature hook-up
Codes
Code 1
(cont.)
6136330
Codes