62
Coding in the delivered condition
Possible change
Economy function room temperature
b5:0
With remote control: No room tem-
perature-dependent heating circuit
pump logic function (change code
only for heating circuit with mixer)
b5:1
to
b5:8
For heating circuit pump logic func-
tion, see the following table:
Parameter address
b5:...
With heating circuit pump logic function:
Heating circuit pump "OFF"
Heating circuit pump "ON"
1
RT
actual
> RT
set
+ 5 K
RT
actual
< RT
set
+ 4 K
2
RT
actual
> RT
set
+ 4 K
RT
actual
< RT
set
+ 3 K
3
RT
actual
> RT
set
+ 3 K
RT
actual
< RT
set
+ 2 K
4
RT
actual
> RT
set
+ 2 K
RT
actual
< RT
set
+ 1 K
5
RT
actual
> RT
set
+ 1 K
RT
actual
< RT
set
6
RT
actual
> RT
set
RT
actual
< RT
set
–
1 K
7
RT
actual
> RT
set
–
1 K
RT
actual
< RT
set
–
2 K
8
RT
actual
> RT
set
–
2 K
RT
actual
< RT
set
–
3 K
Coding in the delivered condition
Possible change
Min. flow temperature heating circuit
C5:20
Electronic minimum flow tempera-
ture limit 20 °C
C5:1
to
C5:127
Minimum limit adjustable from 1 to
127 °C (limited by boiler-specific pa-
rameters)
Max. flow temperature heating circuit
C6:74
Electronic maximum flow tempera-
ture limit set to 74 °C
C6:10
to
C6:127
Maximum limit adjustable from 10 to
127 °C (limited by boiler-specific pa-
rameters)
Heating program changeover
d5:0
External operating program
changeover switches operating
program to "Constant operation at
reduced room temperature" or
"Standby mode"
d5:1
The external operating program
changeover switches to "Constant
operation at standard room tempera-
ture" (subject to coding addresses
"3A", "3b" and "3C")
Ext. heating program changeover to heating circuit
d8:0
No operating program changeover
via EA1 extension
d8:1
Operating program changeover via
input DE1 at EA1 extension
d8:2
Operating program changeover via
input DE2 at EA1 extension
d8:3
Operating program changeover via
input DE3 at EA1 extension
Screed drying
F1:0
Screed drying not active
F1:1
to
F1:6
Screed drying can be set with 6 ad-
justable temperature/time profiles
(see page 94)
F1:15
Constant flow temperature 20 °C
Codes
Code 1
(cont.)
6136330
Codes