49
Note
Observe the manufacturer's documentation included
for the activated carbon filter.
Checking the expansion vessel and system pressure
Adjusting the standard burner settings
Note
To be able to adjust the burner, there must be a heat
demand and heat transfer must also be assured.
Standard values for burner adjustment
Note
Check that the service instructions are applicable to
the relevant burner. See applicability information on
the last page and serial no. on the boiler type plate.
Fig. 46
A
Flue gas test port
Rated heating output
at T
F
/T
R
50/30 °C
kW
12.9/19.3
16.1/23.6
19.3/28.9
at T
F
/T
R
80/60 °C
kW
12/18
15/22
18/27
Burner stage
1
2
1
2
1
2
Rated heat input
kW
12.5
18.7
15.6
22.9
18.7
28.1
Oil burner nozzle
Make: Danfoss
Type
80° H LE
80° H LE
80° H LE
Gph
0.40
0.50
0.50
Oil pressure approx.
■
Min.
bar
8
16.5
10
18
8.5
17
MPa
0.8
1.65
1.0
1.8
0.85
1.7
■
Max.
bar
10.5
20
13
22
13.5
25
MPa
1.05
2.0
1.3
2.2
1.35
2.5
Max. permiss. vacuum in
the oil line
bar
kPa
0.35
35
0.35
35
0.35
35
0.35
35
0.35
35
0.35
35
Oil throughput approx.
kg/h
1.05
1.58
1.53
1.92
1.58
2.37
l/h
1.24
1.86
1.80
2.26
1.86
2.78
Commissioning, inspection, maintenance
Checking the activated carbon filter (accessories)