83
Displayed fault
code
System characteristics
Cause
Measures
d8
Control mode
Input DE3 at
EA1 extension reports a
fault.
Remedy fault at affected appliance.
dA
Control mode without room
influence
Short circuit, room tem-
perature sensor, heating
circuit 1 (without mixer)
Check room temperature sensor,
heating circuit 1.
db
Control mode without room
influence
Short circuit, room tem-
perature sensor for heat-
ing circuit 2 (with mixer)
Check room temperature sensor,
heating circuit 2.
dC
Control mode without room
influence
Short circuit, room tem-
perature sensor for heat-
ing circuit 3 (with mixer)
Check room temperature sensor,
heating circuit 3.
dd
Control mode without room
influence
Lead break, room temper-
ature sensor, heating cir-
cuit 1 (without mixer)
Check room temperature sensor,
heating circuit 1 and remote control
settings (see page 97)
dE
Control mode without room
influence
Lead break, room temper-
ature sensor for heating
circuit 2 (with mixer)
Check room temperature sensor,
heating circuit 2 and remote control
settings (see page 97)
dF
Control mode without room
influence
Lead break, room temper-
ature sensor for heating
circuit 3 (with mixer)
Check room temperature sensor,
heating circuit 3 and remote control
settings (see page 97)
E0
Control mode
External LON subscriber
error
Check connections and LON sub-
scribers.
E4
Burner locked out
24 V power supply fault
Replace control unit.
E5
Burner in a fault state
Flame amplifier fault
Press reset button
R
.
Replace the control unit if the burn-
er will not restart.
E6
Burner in a fault state
Oil preheater does not re-
spond within tolerated
time.
Check oil preheater and supply line
and replace if necessary.
Press reset button
R
.
F0
Burner locked out
Communication error,
burner control unit
Replace control unit.
F1
Burner in a fault state
Flue gas temperature lim-
iter has responded.
Check heating system fill level.
Vent the system.
Press reset button
R
after flue sys-
tem has cooled down.
F2
Burner in a fault state
Temperature limiter has
responded.
Check heating system fill level.
Check circulation pump. Vent the
system. Check temperature limiter
and connecting cables.
Press reset button
R
.
F3
Burner in a fault state
Flame signal is already
present at burner start.
Check ignition electrodes, elec-
trode gaps and connecting cables.
Press reset button
R
.
F4
Burner in a fault state
Flame not established at
end of safety time
Check oil supply, ignition electro-
des, electrode gaps and connect-
ing cables.
Check nozzle and solenoid valve
coil.
Correct the settings if necessary.
Clean dirty parts, replace faulty
parts.
Press reset button
R
.
Troubleshooting
Fault codes
(cont.)
6136330
Service