93
Operating program changeover
Code
Changeover via input DE1
d8:1
Changeover via input DE2
d8:2
Changeover via input DE3
d8:3
You can select which direction the operating program
changeover takes in coding address "d5":
Operating program changeover
Code
Changeover towards "Continually reduced" or "Continuous standby mode" (subject
to the selected set value)
d5:0
Changeover towards "Continuous heating mode"
d5:1
The duration of the operating program changeover can
be adjusted in coding address "F2":
Operating program changeover
Code
No operating program changeover
F2:0
Duration of the operating program changeover 1 to 12 h
F2:1 to
F2:12
The operating program changeover remains active for
as long as the contact remains closed, but at least as
long as the duration selected in coding address "F2".
External blocking
The functions "External blocking" and "External block-
ing with fault message input" are implemented via the
EA1 extension. There are 3 inputs available at the EA1
extension (DE1 to DE3).
The function is selected via the following codes:
External blocking
Code
Input DE1
3A:3
Input DE2
3b:3
Input DE3
3C:3
External blocking and fault message input
Code
Input DE1
3A:4
Input DE2
3b:4
Input DE3
3C:4
The effect on the relevant heating circuit pump is
selected with coding address "d6".
External demand
The "External demand" function is implemented via the
EA1 extension. There are 3 inputs available at the EA1
extension (DE1 to DE3).
The function is selected via the following codes:
Function description
Control functions
(cont.)
6136330
Service