69
Coding in the delivered condition
Possible change
59:0
Cylinder heating:
Start point -2.5 K
Stop point +2.5 K
59:1
to
59:10
Start point adjustable from 1 to 10 K
below set value
5E:0
Circulation pump for cylinder heat-
ing stays in control mode at "Exter-
nal blocking" signal.
5E:1
Circulation pump for cylinder heating
is switched off at "External blocking"
signal.
5E:2
Circulation pump for cylinder heating
is switched on at "External blocking"
signal.
5F:0
Circulation pump for cylinder heat-
ing stays in control mode at "Exter-
nal demand" signal.
5F:1
Circulation pump for cylinder heating
is switched off at "External demand"
signal.
5F:2
Circulation pump for cylinder heating
is switched on at "External demand"
signal.
60:20
During DHW heating, the boiler
water temperature is max. 20 K
higher than the set DHW tempera-
ture.
60:5
to
60:25
The differential between the boiler
water temperature and the set DHW
temperature is adjustable from 5 to
25 K
62:2
Circulation pump with 2 min run-on
time after cylinder heating
62:0
No circulation pump run-on
62:1
to
62:15
Run-on time adjustable from 1 to
15 min
65:0
Do not adjust!
67:40
For solar DHW heating: Set DHW
temperature 40 °C. Reheating by
the DHW cylinder is suppressed
above the selected set tempera-
ture.
67:0
to
67:95
Set DHW temperature adjustable
from 0 to 95 °C (limited by boiler-
specific parameters)
6F:...
Max. heating output for DHW heat-
ing in %, specified by boiler coding
card
6F:0
to
6F:100
Max. heating output for DHW heat-
ing adjustable from min. heating out-
put to 100 %
71:0
DHW circulation pump: "ON" ac-
cording to time program
71:1
"OFF" during DHW heating to set
value 1
71:2
"ON" during DHW heating to set val-
ue 1
72:0
DHW circulation pump: "ON" ac-
cording to time program
72:1
"OFF" during DHW heating to set
value 2
72:2
"ON" during DHW heating to set val-
ue 2
73:0
DHW circulation pump: "ON" ac-
cording to time program
73:1
to
73:6
"ON" from once per hour for 5 min
up to 6 times per hour for 5 min dur-
ing the time program
73:7
Constantly "ON"
"Solar"
Select
"Solar"
(see page 63).
Note
The solar group is only displayed if a solar control
module, type SM1, is connected.
Codes
Code 2
(cont.)
6136330
Codes