63
Coding in the delivered condition
Possible change
Party mode time limit
F2:8
Time limit for party mode or exter-
nal operating program changeover
via pushbutton: 8 h
*2
F2:0
No time limit for party mode
*2
F2:1
to
F2:12
Time limit adjustable from 1 to 12 h
*2
Start temperature raising
F8:-5
Temperature limit for terminating
reduced mode -5 °C; see example
on page 95.
Observe setting of coding address
"A3".
F8:+10
to
F8:-60
Temperature limit adjustable from
+10 to -60 °C
F8:-61
Function inactive
End temperature raising
F9:-14
Temperature limit for raising the re-
duced set room temperature
-14 °C; see example on page 95.
F9:+10
to
F9:-60
Temperature limit for raising the set
room temperature to the value se-
lected for standard mode adjustable
from
+10 to -60 °C
Set flow temperature increase
FA:20
The set boiler water or flow tem-
perature is increased by 20 %
when changing from operation with
reduced room temperature to oper-
ation with standard room tempera-
ture. See example on page 96.
FA:0
to
FA:50
Temperature increase adjustable
from 0 to 50 %
Duration set flow temperature increase
Fb:30
Duration of the set boiler water or
flow temperature increase (see
coding address "FA") 60 min. See
example on page 96.
Fb:0
to
Fb:150
Duration adjustable from 0 to
300 min
1 step
≙
2 min)
Code 2
■
In coding level 2
all
codes are accessible.
■
Codes that are not assigned, due to the heating sys-
tem equipment level or the setting of other codes,
are not displayed.
■
Below, the heating circuit without mixer is designated
"Heating circuit 1"
and the heating circuits with
mixer as
"Heating circuit 2"
or
"Heating circuit 3"
.
If the heating circuits were given individual designa-
tions, the selected designation and
"HC1"
,
"HC2"
or
"HC3"
appear instead.
The codes are divided into groups
■
"General"
■
"Boiler"
■
"DHW"
■
"Solar"
■
"Heating circuit 1/2/3"
■
"All codes std device"
In this group, all coding addresses (except the cod-
ing addresses from the
"Solar"
group) are displayed
in ascending order.
■
"Standard setting"
Calling up code 2
Service menu:
1.
Press
OK
and
simultaneously for approx. 4 s.
2.
Press
OK
and simultaneously for approx. 4 s.
3. "Coding level 2"
4.
Select the group of required coding addresses.
5.
Select the coding address.
*2
In the "Heating and DHW" program, party mode ends
automatically
when the system changes over to operation at stand-
ard room temperature.
Codes
Code 1
(cont.)
6136330
Codes