94
External demand
Code
Input DE1
3A:2
Input DE2
3b:2
Input DE3
3C:2
The effect on the relevant heating circuit pump is
selected with coding address "d7".
The set minimum boiler water temperature for ext.
demand is selected in coding address "9b".
Screed drying
The screed drying function enables screeds to be
dried. For this, always observe the details specified by
the screed manufacturer.
When screed drying is activated, the heating circuit
pump of the mixer circuit is switched on and the flow
temperature is held in accordance with the selected
profile. After completion (30 days), the mixer circuit will
automatically be regulated via the set parameters
again.
Observe EN 1264. The report to be provided by the
heating contractor must contain the following details
regarding heat-up:
■
Heat-up data with the relevant flow temperatures
■
Max. flow temperature achieved
■
Operating state and outside temperature at handover
The various temperature profiles are adjustable via
coding address "F1".
The function continues after a power failure or after the
control unit has been switched off. "Heating and DHW"
is started when screed drying is finished or if code
"F1:0" is set manually.
Temperature profile 1: (EN 1264-4) code "F1:1"
Flow temperature
°C
1
5
10
15
20
25
30
Days
50
40
30
20
10
Fig. 68
Temperature profile 2: (ZV parquet and flooring technology) code "F1:2"
Flow temperature
°C
Days
50
40
30
20
10
1
5
10
15
20
25
30
Fig. 69
Temperature profile 3: Code "F1:3"
Flow temperature
°C
Days
50
40
30
20
10
1
5
10
15
20
25
30
Fig. 70
Function description
Control functions
(cont.)
6136330