Vertiv | Liebert CRV CCD10 Condenser | User Manual
16
Mechanical Installation
2.3.2
Horizontal airflow installation
S= Airflow passage equivalent to or larger than the frontal surface.
Figure 2-4 Horizontal airflow installation space requirements
Table 2-2 Horizontal airflow installation space dimensions
Condenser Model
Dimensions (inch [mm])
D
E
CCD100S-00A
500 [19.7]
300 [11.8]
CCD101S-00A
500 [19.7]
300 [11.8]
Figure 2-5 Multiple Outdoor Units Placed in Overlap Mode
Airflow
Airflow
Bracket
50mm
[2.0in.]
50mm [2.0in.]
Min.50mm [2.0in.]
Base
Outdoor unit base
4m [13.1ft]
0.5m [1.6ft]
Note:
1. Use 5# angle iron for bracket, when
two units are installed with one above
the other.
2.Use 6.5# channel steel for bracket, when
three units are installed with one above
the other.
a)
b)
c)
S
S
≥
D
≥
E
Out-
door
unit
Out-
door
unit