Vertiv | Liebert CRV CCD10 Condenser | User Manual
6
Overview
1.3.5
Check valve
An auxiliary check valve should be used in the liquid line between the head pressure valve and the receiver to prevent
the refrigerant migration to condenser. Pay attention to the arrow on the valve body as the arrow indicates the flow
direction of the refrigerant in the valve. Ensure that the arrow points towards the liquid receiver.
Figure 1-7 The check valve