Vertiv | Liebert CRV CCD10 Condenser | User Manual
15
Mechanical Installation
2.3
Space Requirements
NOTE: A 4000 mm [157.5 in.] clearance is required above the condenser air outlet.
The condenser needs sufficient installation and service space around the installation place. The condenser installation
space requirements are as follows:
2.3.1
Vertical airflow installation
Figure 2-3 Vertical airflow installation space requirements
Table 2-1 Vertical airflow installation space dimensions
Condenser Model
Dimensions (mm[inch])
A
B
C
CCD100S-00A
915 [36]
915 [36]
800 [31.5]
CCD101S-00A
915 [36]
915 [36]
800 [31.5]
A
B
B
A
C
B
B
B
B
C