Vertiv | Liebert CRV CCD10 Condenser | User Manual
27
Maintenance and Troubleshooting
3.2
Troubleshooting
Perform troubleshooting according to Table 3-1.
Table 3-1 Table of Alarm Troubleshooting
Fault Phenomenon
Possible Causes
Handling Method
Equipment does not
start up
Equipment does not connect to the
power supply
Check the input voltage
High pressure alarm
Insufficient condenser air flow
Clean away the alien objects on the coil surface or near the air
inlet, and check the fan speed regulation function of the
control board
Condenser fan does not run
Check if the cable connection between the control board and
outdoor unit terminals is loosened, check if the outdoor unit
cable connection is loosened, and check if the condenser
pressure sensor is normal