Mechanical Installation
2.2
Installation Notes
1.
The outdoor unit should be installed in a place that is convenient for maintenance. Do not install the outdoor unit
at the bottom layer of the public place and the unit should be installed far away from the residential area.
2.
Do not directly install the outdoor unit in the environment with noise restrictions.
3.
To ensure the heat dissipation capacity, install the condenser in a clean place that is far away from dusts and
foreign objects to avoid obstruct the heat exchanger.
4.
Do not place the unit close to vapors, hot gases and waste gases.
5.
Keep at least 500 mm [19.7 in.] clearance between the outdoor unit and the wall, barrier or neighboring
equipment.
6.
Do not place the unit at the air inlet side and air discharge side where snow may be accumulated.
7.
Prepare a base that can withstand the weight of the outdoor unit (see Table 1-1 for the specific weight). The
height of the base should be at least 50 mm [2 in.] above the ground and should be higher than the base of unit by
50 mm [2 in.], as shown in Figure 2-4.
8.
When multiple outdoor units need to be placed in overlap mode, install according to the mode as shown in Figure
2-4.
9.
In order to ensure the performance of the unit, priority is given to vertical airflow installation of the outdoor unit.
10.
Only vertical airflow is allowed for the condenser with Low Ambient Kit, and the Low Ambient Kit should be
mounted in the condenser legs for proper operation.