Overview
1.5
Parameters of Operating Environment
Table 1-3 defines the operating condition parameters including the ambient temperature, protection level, altitude
and voltage range.
Table 1-3 Parameters of Operation Environment
Items
Requirements
Installation
position
The maximum equivalent pipe length between the indoor unit and the condenser is 91.4 m
[300ft.]. Vertical difference*
Δ
H: -8 m [-26.2 ft.
] ≤
Δ
H ≤
30 m [98.4 ft.].
Installation
mode
Standard condenser
:
Horizontal airflow installation and vertical airflow installation
The condenser with Low Ambient Kit
:
vertical airflow installation
Ambient
temperature
5 °F to 113 °F [-15 °C to +45 °C].
-29.2 °F to 113 °F [-
34
°C to +45 °C] with Low Ambient Kit.
Ambient
humidity
Outdoor: 5% RH to 95% RH
Operation
power
CCD100S: 208 V/ 230 V ±10%, 1 Ph, 60 Hz;
CCD101S: 230 V ±10%, 1 Ph, 50/60 Hz
Altitude
≤
2000 m [6562 ft.]. Derating is required if the altitude exceeds 2000 m [6562 ft.]
Protection
level
IPX4
Note*: The value is positive if the condenser is installed higher than the indoor unit; otherwise the value is
negative.
1.6
Parameters of Storage Environment
Table 1-4 defines the Storage condition parameters including the ambient humidity, ambient temperature, and storage
time conditions.
Table 1-4 Parameters of Storage Environment
Items
Requirements
Storage environment
Clean indoor environment with good ventilation and no dust
Ambient temperature -40 °F to 158 °F [-40 °C to +70 °C]
Ambient
humidity
5% RH to 95% RH
Storage time
The total storage time should not exceed 6 months. Otherwise, the performance needs to
be re-calibrated