manualshive.com logo in svg
background image

Z206855-0B 

Page 7 of 26 

©2014 Veris Industries   USA 800.354.8556 or +1.503.598.4564  / [email protected] 04142 

Alta Labs, Enercept, Enspector, Hawkeye, Trustat, Aerospond, Veris, and the Veris ‘V’ logo are trademarks or registered trademarks of  Veris Industries, L.L.C. in the USA and/or other countries.

Other companies’ trademarks are hereby acknowledged to belong to their respective owners.

Installation Guide

Power Monitoring

E31E Series

TM

Installation

Observe precautions for handling static sensitive

devices to avoid damage to the circuitry that

is not covered under the factory warranty.

 Disconnect power to the panel before beginning the installation.

1.  Locate a surface inside the electrical enclosure to mount the E31E. Decide whether to mount the E31E vertically or horizontally. 

The E31E is shipped with the brackets placed for vertical mounting. If mounting horizontally, loosen the screws on the sides of 

the E31E that hold the brackets in place (do not fully remove the screws from the E31E housing). Loosen the screws on the other 

two sides of the housing (do not fully remove the screws from the E31E housing), and set the brackets into their new positions. 

Tighten all screws.

Vertical Mounting                         Horizontal Mounting

2.  Install the E31E in the panel (hardware not provided). A grounding connection is located on the housing (see below). Use this 

stud to ground the device when it is mounted on a nonconductive surface. 

CURRENT SENSOR STRIP

CURRENT SENSOR STRIP

CURRENT SENSOR STRIP

CURRENT SENSOR STRIP

Panel 2

Panel 1

E31E

             

Ground

Split-Core Current 
Sensors

50 A Split-Core CT

100 A Split-Core CT

200 A Split-Core CT

Voltage Rating 300 VAC

300 VAC (CE), 600 VAC (UL)

300 VAC (CE), 600 VAC (UL)

Accuracy

±1%

±0.5%

±1%

Temperature

0° to 60°C

0° to 60°C

0° to 60°C

Agency

UL 61010-1 Recognized, EN61010-1 UL 61010-1 Recognized, EN61010-1 UL 61010-1 Recognized, EN61010-1

Shop for Power Metering products online at:

1.888.610.7664

www.

PowerMeterStore

.com

Содержание E31A002

Страница 1: ...or serious injury A qualified person is one who has skills and knowledge related to the construction and operation of this electrical equipment and the installation and has received safety training to...

Страница 2: ...z Update Rate Modbus 1 8 seconds both panels BACnet 14 seconds SNMP 20 seconds ETHERNET COMMUNICATION Physical Interface RJ45 connector with 10 100 Mbit Ethernet Protocols Supported Modbus TCP BACnet...

Страница 3: ...p A 1 0 26 mm B 0 5 11 mm C 0 4 10 mm D 0 9 23 mm E 1 6 40 mm E31CT1 100 Amp A 1 5 39 mm B 0 8 20 mm C 0 7 16 mm D 1 6 40 mm E 2 1 53 mm E31CT3 200 Amp A 1 5 39 mm B 1 25 32 mm C 1 25 32 mm D 2 5 64 m...

Страница 4: ...gh amperage source Inputs on the left are for panelboard 2 inputs on the right are for panelboard 1 8 50 Pin Ribbon Cable Connectors 4 foot 0 9 m ribbon cables are provided for easy connection of the...

Страница 5: ...62017 BACnet object AV164 or SNMP MIB variable spanels panel1 p1Configuration p1Setup p1UserDefinedSettings OID 1 3 6 1 4 1 40845 1 30 1 1 6 3 4 0 For models with 42 channels or more these features a...

Страница 6: ...the RTC resets to a default date and time and must be set again in order to run When using the RTC the demand snapshot interval can be set from 10 to 3600 seconds 1 hour Monitoring of Mains RealTime M...

Страница 7: ...y loosen the screws on the sides of the E31E that hold the brackets in place do not fully remove the screws from the E31E housing Loosen the screws on the other two sides of the housing do not fully r...

Страница 8: ...CK to the mounting surface Click the adapter board into place 4 Install the current sensors onto the conductors to be monitored Orientation Note If the signed power factor feature is NOT enabled then...

Страница 9: ...sororientation doesnotaffectmeterbehavior IfthisfeatureISenabled orientthecurrent sensorssothatthearrowpointstowardthe loadforproperoperation Alignribbon cablekeywith connectorkeyhole 5 Connect the ad...

Страница 10: ...1 10 9 8 7 6 5 4 3 2 1 42 40 38 36 34 32 30 28 26 24 22 20 18 16 14 12 10 8 6 4 2 42 41 40 39 38 37 36 35 34 33 32 31 30 29 28 27 26 24 24 23 22 EVEN SEQ BLACK WHITE Adapter Board B numbering EVEN 2 4...

Страница 11: ...5 to 4 4 in lb 0 4 to 0 5 N m all other terminals 4 4 to 5 3 in lb 0 5 to 0 6 N m 1 Wire the CTs to the E31E Note For Veris CTs X1 is the white lead X2 is the black lead 1 2 3 N X1 X1 X1 X1 X2 X2 X2 X...

Страница 12: ...ment of these resistors varies for each standard The E31E does not implement any RS 485 line polarization bias or termination internally For the RS 485 cable use shielded twisted pair wire such as Bel...

Страница 13: ...ork on the network and is being accessed from a PC on that same network open a web browser and enter the IP address of the E31E into the address URL field on the browser Press enter The GUI launches a...

Страница 14: ...ts factory default IP address of 192 168 1 24 set the PC to an unused static IP address on the 192 168 1 xxx subnet where xxx is any value between 1 and 255 except 24 Set the subnet mask to 255 255 25...

Страница 15: ...following IP Address Make note of the IP address that appears then enter the static IP address e g if the E31E Series is still set to its default address of 192 168 1 24 then change it to 192 168 1 10...

Страница 16: ...llation Guide Power Monitoring E31E Series TM UsingtheGUItosetuptheIPaddressforuseonyournetwork 1 Access the GUI according the instructions in the Accessing the Graphical User Interface GUI section To...

Страница 17: ...ess Settings menu b Enter the desired IP address in the N1_IP_Address field in the format xxx xxx xxx xxx c If necessary change the Subnet Mask by entering the appropriate new value in the N1_Netmask...

Страница 18: ...y mode default deletes profiles and rediscovers them when the device is powered again The results are the same unless the profile configuration is intentionally altered Profile selection and discovery...

Страница 19: ...BACnet devices for each 42 channel meter panel behind this virtual router allowing the devices to be discoverable and independently accessed via BACnet even if the virtual router is connected by MS TP...

Страница 20: ...bject for the E31E s virtual router The final field is the MSTP_MAC_Addr which sets the MAC address for the virtual router The E31E panel s are devices on the internal BACnet network and are not direc...

Страница 21: ...ique parameters The SNMP_Community string is used to control access to the device Whatever value entered must be used in the MIB browser or SNMP access software to communicate with this device The las...

Страница 22: ...ings using the GUI Valid network numbers range from 1 to 65534 if other values are entered the network number defaults to 5 b Device_ID Offset Every BACnet device must have a BACnet Device_ID number t...

Страница 23: ...WritePropertyMultiple B DS WPM B K 1 12 BIBB Data Sharing COV B DS COV B K 2 2 BIBB Alarm and Event Notification Internal B AE N I B K 2 5 BIBB Alarm and Event ACK B AE ACK B K 2 11 BIBB Alarm and Ev...

Страница 24: ...value by writing the Object_name property The E31E supports Subscribe_COV with default COV increment values assigned as shown in the data object tables If these values are not appropriate for a specif...

Страница 25: ...o the Panel 1A and Panel 1B connectors and to the data set under Modbus address 1 or BACnet device identified as Node_1 in the GUI Panel 2 corresponds to the CT strips connected to the Panel 2A and Pa...

Страница 26: ...trip installation Verify phase rotation of breakers firmware rev 1 012 or higher allows for custom rotation if needed Current reading is not as expected or reading is on different CT number than expec...

Отзывы: