Installation Guide

Power Monitoring

E31E Series

TM

4. Mechanically secure the RS-485 cable where it enters the electrical panel.

5. If using Modbus RTU or BACnet MS/TP protocol, connect a serial cable(s) from the RS-485 loop to the serial connector on the 

E31E. Connect all RS-485 devices in a daisy-chain, and properly terminate the chain. Two sets of connections are provided 
to simplify daisy-chain connections and enable retention of each wire. Follow all applicable wiring and termination 
connection guidelines for the standard in use. Note that while both the the Modbus RTU and BACnet MS/TP standards identify 
requirements for RS-485 line polarization/bias and termination, the value and placement of these resistors varies for each 
standard. The E31E does not implement any RS-485 line polarization/bias or termination internally. For the RS-485 cable, 
use shielded, twisted-pair wire, such as Belden 1120A, that is voltage-rated for the installation. The shield is not internally 
connected to Earth Ground. Connect the shield to Earth Ground somewhere on the RS-485 bus (single point connection only).

RS-485

S

+

S

+

Belden 1120A or 

equivalent

120 

Ω

 terminator 

where specified 

by the applicable 

standard

            

WARNING:  After wiring 

the RS-485 cable, remove 

all scraps of wire or foil 

shield from the electrical 

panel. Wire scraps coming 

into contact with high 

voltage conductors could 

be DANGEROUS!

6. Connect an ethernet cable to a local PC. Secure a ferrite filter (included) around the ethernet cable to ensure the device meets 

emission requirements. Use the PC to configure the gateway (next section of this document).

7. Once configured, disconnect the local PC. If desired (and the device is configured for operation on the network), connect the 

E31E directly to the network for ongoing access to the GUI even if primarily using a serial protocol to access and control the 
E31E.

Wiring (cont.)

Shop for Power Metering products online at:

1.888.610.7664

www.

PowerMeterStore

.com

Содержание E31A002

Страница 1: ...or serious injury A qualified person is one who has skills and knowledge related to the construction and operation of this electrical equipment and the installation and has received safety training to...

Страница 2: ...z Update Rate Modbus 1 8 seconds both panels BACnet 14 seconds SNMP 20 seconds ETHERNET COMMUNICATION Physical Interface RJ45 connector with 10 100 Mbit Ethernet Protocols Supported Modbus TCP BACnet...

Страница 3: ...p A 1 0 26 mm B 0 5 11 mm C 0 4 10 mm D 0 9 23 mm E 1 6 40 mm E31CT1 100 Amp A 1 5 39 mm B 0 8 20 mm C 0 7 16 mm D 1 6 40 mm E 2 1 53 mm E31CT3 200 Amp A 1 5 39 mm B 1 25 32 mm C 1 25 32 mm D 2 5 64 m...

Страница 4: ...gh amperage source Inputs on the left are for panelboard 2 inputs on the right are for panelboard 1 8 50 Pin Ribbon Cable Connectors 4 foot 0 9 m ribbon cables are provided for easy connection of the...

Страница 5: ...62017 BACnet object AV164 or SNMP MIB variable spanels panel1 p1Configuration p1Setup p1UserDefinedSettings OID 1 3 6 1 4 1 40845 1 30 1 1 6 3 4 0 For models with 42 channels or more these features a...

Страница 6: ...the RTC resets to a default date and time and must be set again in order to run When using the RTC the demand snapshot interval can be set from 10 to 3600 seconds 1 hour Monitoring of Mains RealTime M...

Страница 7: ...y loosen the screws on the sides of the E31E that hold the brackets in place do not fully remove the screws from the E31E housing Loosen the screws on the other two sides of the housing do not fully r...

Страница 8: ...CK to the mounting surface Click the adapter board into place 4 Install the current sensors onto the conductors to be monitored Orientation Note If the signed power factor feature is NOT enabled then...

Страница 9: ...sororientation doesnotaffectmeterbehavior IfthisfeatureISenabled orientthecurrent sensorssothatthearrowpointstowardthe loadforproperoperation Alignribbon cablekeywith connectorkeyhole 5 Connect the ad...

Страница 10: ...1 10 9 8 7 6 5 4 3 2 1 42 40 38 36 34 32 30 28 26 24 22 20 18 16 14 12 10 8 6 4 2 42 41 40 39 38 37 36 35 34 33 32 31 30 29 28 27 26 24 24 23 22 EVEN SEQ BLACK WHITE Adapter Board B numbering EVEN 2 4...

Страница 11: ...5 to 4 4 in lb 0 4 to 0 5 N m all other terminals 4 4 to 5 3 in lb 0 5 to 0 6 N m 1 Wire the CTs to the E31E Note For Veris CTs X1 is the white lead X2 is the black lead 1 2 3 N X1 X1 X1 X1 X2 X2 X2 X...

Страница 12: ...ment of these resistors varies for each standard The E31E does not implement any RS 485 line polarization bias or termination internally For the RS 485 cable use shielded twisted pair wire such as Bel...

Страница 13: ...ork on the network and is being accessed from a PC on that same network open a web browser and enter the IP address of the E31E into the address URL field on the browser Press enter The GUI launches a...

Страница 14: ...ts factory default IP address of 192 168 1 24 set the PC to an unused static IP address on the 192 168 1 xxx subnet where xxx is any value between 1 and 255 except 24 Set the subnet mask to 255 255 25...

Страница 15: ...following IP Address Make note of the IP address that appears then enter the static IP address e g if the E31E Series is still set to its default address of 192 168 1 24 then change it to 192 168 1 10...

Страница 16: ...llation Guide Power Monitoring E31E Series TM UsingtheGUItosetuptheIPaddressforuseonyournetwork 1 Access the GUI according the instructions in the Accessing the Graphical User Interface GUI section To...

Страница 17: ...ess Settings menu b Enter the desired IP address in the N1_IP_Address field in the format xxx xxx xxx xxx c If necessary change the Subnet Mask by entering the appropriate new value in the N1_Netmask...

Страница 18: ...y mode default deletes profiles and rediscovers them when the device is powered again The results are the same unless the profile configuration is intentionally altered Profile selection and discovery...

Страница 19: ...BACnet devices for each 42 channel meter panel behind this virtual router allowing the devices to be discoverable and independently accessed via BACnet even if the virtual router is connected by MS TP...

Страница 20: ...bject for the E31E s virtual router The final field is the MSTP_MAC_Addr which sets the MAC address for the virtual router The E31E panel s are devices on the internal BACnet network and are not direc...

Страница 21: ...ique parameters The SNMP_Community string is used to control access to the device Whatever value entered must be used in the MIB browser or SNMP access software to communicate with this device The las...

Страница 22: ...ings using the GUI Valid network numbers range from 1 to 65534 if other values are entered the network number defaults to 5 b Device_ID Offset Every BACnet device must have a BACnet Device_ID number t...

Страница 23: ...WritePropertyMultiple B DS WPM B K 1 12 BIBB Data Sharing COV B DS COV B K 2 2 BIBB Alarm and Event Notification Internal B AE N I B K 2 5 BIBB Alarm and Event ACK B AE ACK B K 2 11 BIBB Alarm and Ev...

Страница 24: ...value by writing the Object_name property The E31E supports Subscribe_COV with default COV increment values assigned as shown in the data object tables If these values are not appropriate for a specif...

Страница 25: ...o the Panel 1A and Panel 1B connectors and to the data set under Modbus address 1 or BACnet device identified as Node_1 in the GUI Panel 2 corresponds to the CT strips connected to the Panel 2A and Pa...

Страница 26: ...trip installation Verify phase rotation of breakers firmware rev 1 012 or higher allows for custom rotation if needed Current reading is not as expected or reading is on different CT number than expec...

Отзывы: