Installation Guide

Power Monitoring

E31E Series

TM

Using the GUI to Set the Configuration Parameters for the Communication Protocols

Access the GUI according the instructions in the “Accessing the Graphical User Interface (GUI)” section.

The home screen on the GUI provides fields for configuration of the E31E. The E31E has four primary modes of operation, each of 
which support a different combination of protocols. Each option field has a Submit button to the right. When changing the value 
in any field, click Submit to store the new value. The GUI prompts the user to restart the system. If multiple values are changed, 
it is easiest to submit all changes and restart only once when finished with the whole screen. To restart, click the System Restart 
button in the row at the bottom of the screen. The restart takes several seconds, during which the server may lose its connection. 
Messages appear at the top of the screen indicating current status, but do not perform any actions. Simply allow the tool to 
complete the restart cycle. 

The first selection in the GUI is Operating_Mode, which has two choices:

1. Locked:  used for all normal product operation. It is provided as a tool for high-level technical support. The gateway retains 
its current profile configuration when powered. 
2. Discovery mode (default):  deletes profiles and rediscovers them when the device is powered again. The results are the same, 
unless the profile configuration is intentionally altered. Profile selection and discovery are especially important when using 
BACnet or SNMP protocols. For normal operation, always use discovery mode.

The second selection in the GUI is Protocol_Mode, used to select the combination of protocols the product communicates with. 
The E31E supports five protocols, some of which can operate simultaneously. The table below shows what protocols are supported 
in each mode.

Protocol Mode

Primary Protocol

Ethernet Protocol

RS-485 Protocol

1

BACnet MS/TP

Modbus TCP

BACnet MS/TP

2

BACnet IP

BACnet IP/Modbus TCP

Modbus RTU

3

SNMP

SNMP/Modbus TCP

Modbus RTU

4

Modbus

Modbus TCP

Modbus RTU

To select a primary protocol mode, enter the corresponding number into the text field adjacent to the Primary Protocol option 
and click the Submit button to the left of the text field. A prompt appears at the top of the screen instructing the user to restart 
the system. When finished, the screen refreshes itself with the appropriate fields for the selected mode. 

The next GUI selection, in any protocol mode, is the Upstream_Baud rate selection. If you have selected BACnet MS/TP (mode 1) as 
the primary protocol mode, this value sets the MS/TP baud rate. If you have selected modes 2 or 3 as the primary protocol mode, 
you may not be using the RS-485 interface at all. If so, this setting can be ignored.

If you have selected BACnet IP, SNMP or Modbus mode, the next selection is Modbus_Parity, which sets the parity of the upstream 
serial connection. If using Modbus RTU protocol, set this to match your Modbus master. If not, ignore this field.

Gateway 
Configuration (cont.)

Shop for Power Metering products online at:

1.888.610.7664

www.

PowerMeterStore

.com

Содержание E31A002

Страница 1: ...or serious injury A qualified person is one who has skills and knowledge related to the construction and operation of this electrical equipment and the installation and has received safety training to...

Страница 2: ...z Update Rate Modbus 1 8 seconds both panels BACnet 14 seconds SNMP 20 seconds ETHERNET COMMUNICATION Physical Interface RJ45 connector with 10 100 Mbit Ethernet Protocols Supported Modbus TCP BACnet...

Страница 3: ...p A 1 0 26 mm B 0 5 11 mm C 0 4 10 mm D 0 9 23 mm E 1 6 40 mm E31CT1 100 Amp A 1 5 39 mm B 0 8 20 mm C 0 7 16 mm D 1 6 40 mm E 2 1 53 mm E31CT3 200 Amp A 1 5 39 mm B 1 25 32 mm C 1 25 32 mm D 2 5 64 m...

Страница 4: ...gh amperage source Inputs on the left are for panelboard 2 inputs on the right are for panelboard 1 8 50 Pin Ribbon Cable Connectors 4 foot 0 9 m ribbon cables are provided for easy connection of the...

Страница 5: ...62017 BACnet object AV164 or SNMP MIB variable spanels panel1 p1Configuration p1Setup p1UserDefinedSettings OID 1 3 6 1 4 1 40845 1 30 1 1 6 3 4 0 For models with 42 channels or more these features a...

Страница 6: ...the RTC resets to a default date and time and must be set again in order to run When using the RTC the demand snapshot interval can be set from 10 to 3600 seconds 1 hour Monitoring of Mains RealTime M...

Страница 7: ...y loosen the screws on the sides of the E31E that hold the brackets in place do not fully remove the screws from the E31E housing Loosen the screws on the other two sides of the housing do not fully r...

Страница 8: ...CK to the mounting surface Click the adapter board into place 4 Install the current sensors onto the conductors to be monitored Orientation Note If the signed power factor feature is NOT enabled then...

Страница 9: ...sororientation doesnotaffectmeterbehavior IfthisfeatureISenabled orientthecurrent sensorssothatthearrowpointstowardthe loadforproperoperation Alignribbon cablekeywith connectorkeyhole 5 Connect the ad...

Страница 10: ...1 10 9 8 7 6 5 4 3 2 1 42 40 38 36 34 32 30 28 26 24 22 20 18 16 14 12 10 8 6 4 2 42 41 40 39 38 37 36 35 34 33 32 31 30 29 28 27 26 24 24 23 22 EVEN SEQ BLACK WHITE Adapter Board B numbering EVEN 2 4...

Страница 11: ...5 to 4 4 in lb 0 4 to 0 5 N m all other terminals 4 4 to 5 3 in lb 0 5 to 0 6 N m 1 Wire the CTs to the E31E Note For Veris CTs X1 is the white lead X2 is the black lead 1 2 3 N X1 X1 X1 X1 X2 X2 X2 X...

Страница 12: ...ment of these resistors varies for each standard The E31E does not implement any RS 485 line polarization bias or termination internally For the RS 485 cable use shielded twisted pair wire such as Bel...

Страница 13: ...ork on the network and is being accessed from a PC on that same network open a web browser and enter the IP address of the E31E into the address URL field on the browser Press enter The GUI launches a...

Страница 14: ...ts factory default IP address of 192 168 1 24 set the PC to an unused static IP address on the 192 168 1 xxx subnet where xxx is any value between 1 and 255 except 24 Set the subnet mask to 255 255 25...

Страница 15: ...following IP Address Make note of the IP address that appears then enter the static IP address e g if the E31E Series is still set to its default address of 192 168 1 24 then change it to 192 168 1 10...

Страница 16: ...llation Guide Power Monitoring E31E Series TM UsingtheGUItosetuptheIPaddressforuseonyournetwork 1 Access the GUI according the instructions in the Accessing the Graphical User Interface GUI section To...

Страница 17: ...ess Settings menu b Enter the desired IP address in the N1_IP_Address field in the format xxx xxx xxx xxx c If necessary change the Subnet Mask by entering the appropriate new value in the N1_Netmask...

Страница 18: ...y mode default deletes profiles and rediscovers them when the device is powered again The results are the same unless the profile configuration is intentionally altered Profile selection and discovery...

Страница 19: ...BACnet devices for each 42 channel meter panel behind this virtual router allowing the devices to be discoverable and independently accessed via BACnet even if the virtual router is connected by MS TP...

Страница 20: ...bject for the E31E s virtual router The final field is the MSTP_MAC_Addr which sets the MAC address for the virtual router The E31E panel s are devices on the internal BACnet network and are not direc...

Страница 21: ...ique parameters The SNMP_Community string is used to control access to the device Whatever value entered must be used in the MIB browser or SNMP access software to communicate with this device The las...

Страница 22: ...ings using the GUI Valid network numbers range from 1 to 65534 if other values are entered the network number defaults to 5 b Device_ID Offset Every BACnet device must have a BACnet Device_ID number t...

Страница 23: ...WritePropertyMultiple B DS WPM B K 1 12 BIBB Data Sharing COV B DS COV B K 2 2 BIBB Alarm and Event Notification Internal B AE N I B K 2 5 BIBB Alarm and Event ACK B AE ACK B K 2 11 BIBB Alarm and Ev...

Страница 24: ...value by writing the Object_name property The E31E supports Subscribe_COV with default COV increment values assigned as shown in the data object tables If these values are not appropriate for a specif...

Страница 25: ...o the Panel 1A and Panel 1B connectors and to the data set under Modbus address 1 or BACnet device identified as Node_1 in the GUI Panel 2 corresponds to the CT strips connected to the Panel 2A and Pa...

Страница 26: ...trip installation Verify phase rotation of breakers firmware rev 1 012 or higher allows for custom rotation if needed Current reading is not as expected or reading is on different CT number than expec...

Отзывы: