
Z206855-0B
Page 19 of 26
©2014 Veris Industries USA 800.354.8556 or +1.503.598.4564 / [email protected] 04142
Alta Labs, Enercept, Enspector, Hawkeye, Trustat, Aerospond, Veris, and the Veris ‘V’ logo are trademarks or registered trademarks of Veris Industries, L.L.C. in the USA and/or other countries.
Other companies’ trademarks are hereby acknowledged to belong to their respective owners.
Installation Guide
Power Monitoring
E31E Series
TM
The following sections show the field selections (with factory default values) specific to each of the four Protocol_Modes.
1. BACnet MS/TP mode
The first three options are discussed previously.
The DeviceID_Offset parameter is used to assign Device_IDs on power-up or on restart until they have been overwritten via
BACnet. Enter a different value here and click submit. The new value is first used at the next power-up or system restart. Valid
Device_ID numbers range from 1 to 4194303. Since the numbers assigned during discovery are the sum of the Offset and the
Modbus address (which can be any value from 1-255), the Offset values entered in the GUI must be no larger than 4194055.
The E31E gateway creates a BACnet virtual router and separate BACnet devices for each 42-channel meter panel behind this virtual
router, allowing the devices to be discoverable and independently accessed via BACnet, even if the virtual router is connected by
MS/TP, using a single MAC address. To use this product with MS/TP, the BACnet system must support the discovery and use of a
BACnet router on the MS/TP trunk and any devices beyond it. This virtual router creates an exclusive BACnet network on which
the meter’s BACnet devices reside. This network must have a BACnet network number that is different from any other networks in
the entire BACnet enterprise. When multiple E31E products are added anywhere in the enterprise, each one must have a unique
network number. Failure to set an exclusive value in this field causes communication conflicts in the BACnet system.
Enter a non-conflicting value here and click submit. Valid network numbers range from 1 to 65534; if other values are entered,
the network number defaults to 5. The new value is first used at the next power-up or system restart. If using an external BACnet
router to connect the E31E as an MS/TP device, it is recommended that the router also be restarted after the E31E has completed
discovery, when the network number is changed.
Gateway
Configuration (cont.)
Shop for Power Metering products online at:
1.888.610.7664
www.
PowerMeterStore
.com