The safety devices must be checked prior to initial start-up and at
the specified intervals.
Tab. 8: Interval
t
Every day
w
Every week
m
Every month
j
Every year
Tab. 9: Inspection
S
Visual inspection
F
Function check
M
Measurement
CAUTION!
Built-in safety devices
The built-in safety devices must only be checked/
replaced by a VEIT service engineer or by trained
and instructed skilled personnel.
NOTICE!
Pump runtime monitoring
The pump runtime is monitored by the electronics.
When a specified maximum time (4-5 minutes) is
exceeded, an audible signal is triggered. Switching
the device off and back on again acknowledges the
fault and restarts the pump runtime. The cause of
the fault must be removed (see chapter “Remedy
of faults/elimination of defects”).
Additional safety function
Safety
Built-in safety devices
30.09.2022
Steam generator VEIT SG67
19