FIBERTRAC 31 • Profibus PA
43833-EN-170126
Output variable - Level measurement
Output
Ʋ Output signal
digital output signal, format according to IEEE-754
Ʋ Sensor address
126 (default setting)
Damping (63 % of the input variable)
0 … 999 s, adjustable
Profibus PA profile
3.02
Number of FBs with AI (function blocks
with analogue input)
3
Default values
Ʋ
1. FB
PV
Ʋ
2. FB
Electronics temperature
Ʋ
3. FB
Pulse rate
Current value
10 mA, ±0.5 mA
Output variable - Level detection
Output
Ʋ Output signal
digital output signal, format according to IEEE-754
Ʋ Sensor address
126 (default setting)
Damping (63 % of the input variable)
0 … 999 s, adjustable
Profibus PA profile
3.02
Number of FBs with AI (function blocks
with analogue input)
3
Default values
Ʋ
1. FB
PV
Ʋ
2. FB
Electronics temperature
Ʋ
3. FB
Pulse rate
Current value
10 mA, ±0.5 mA
Relay output
Output
Relay output (SPDT), floating spdt
Switching voltage
Ʋ
Min.
10 mV
Ʋ
Max.
253 V AC, 253 V DC
Switching current
Ʋ
Min.
10 µA
Ʋ
Max.
3 A AC, 1 A DC
Breaking capacity
Ʋ
Min.
50 mW
Ʋ
Max.
750 VA AC, 40 W DC
If inductive loads or stronger currents are switched
through, the gold plating on the relay contact surface will
be permanently damaged. The contact is then no longer
suitable for switching low-level signal circuits.