11 Diagnostics and servicing
FIBERTRAC 31 • Profibus PA
43833-EN-170126
11 Diagnostics and servicing
11.1 Maintenance
If the instrument is used correctly, no maintenance is required in
normal operation.
The corresponding source container must be checked in regular
intervals. You can find further information in the operating instructions
manual of the source container.
11.2 Status messages
The instrument features self-monitoring and diagnostics according to
NE 107 and VDI/VDE 2650. In addition to the status messages in the
following tables, detailed error messages are available under menu
item "
Diagnostics
" via the display and adjustment module, PACTware/
DTM and EDD.
The status messages are divided into the following categories:
•
Failure
•
Function check
•
Out of specification
•
Maintenance requirement
and explained by pictographs:
4
1
2
3
Fig. 26: Pictographs of the status messages
1 Failure - red
2 Out of specification - yellow
3 Function check - orange
4 Maintenance - blue
Failure:
Due to a malfunction in the instrument, a failure message is
outputted.
This status message is always active. It cannot be deactivated by the
user.
Function check:
The instrument is being worked on, the measured
value is temporarily invalid (for example during simulation).
This status message is inactive by default. It can be activated by the
user via PACTware/DTM or EDD.
Out of specification:
The measured value is unreliable because an
instrument specification was exceeded (e.g. electronics temperature).
This status message is inactive by default. It can be activated by the
user via PACTware/DTM or EDD.
Maintenance:
Due to external influences, the instrument function
is limited. The measurement is affected, but the measured value is
Status messages