6 Set up with the display and adjustment module
FIBERTRAC 31 • Profibus PA
43833-EN-170126
Caution:
When the PIN is active, adjustment via PACTware/DTM as well as
other systems is also blocked.
In delivery status, the PIN is
0000.
Call our service department if you have modified and forgotten the
PIN.
Additional settings
When a reset is carried out, all settings (with only a few exceptions)
are reset. The exceptions are: PIN, language, SIL and HART mode.
The following reset functions are available:
Basic settings:
Resetting of the parameter adjustments to default
values at the time of shipment. Order-specific settings are deleted.
Default settings:
Resetting of the parameter adjustment like under
"
Basic settings
". In addition, special parameters are reset to default
values. Order-specific settings are deleted.
Peak values of measured value:
Resetting of the parameter adjust
-
ments in the menu item "
Setup
" to the default values of the respective
instrument. Order-specific settings remain but are not taken over into
the current parameters.
Peak values of temperature:
Resetting of the measured min. and
max. temperatures to the actual measured value.
The following table shows the default values of the instrument. The
values apply for the application "
Summation Slave
". The application
must be selected first.
Depending on the instrument version, not all menu items may be
available or they may be differently assigned:
Menu
Menu item
Default value
Setup
Sensor address
126
Measurement loop name
Sensor
Isotope
Cs-137
Application
Summation Slave
Outputs
Deactivated
AI FB1 Channel
Process value
AI FB1 scaling unit
%
AI FB1 scaling
0 % = 0 %
100 % = 100 %
AI FB1 damping
0 s
Lock adjustment
Released
Additional settings -
Reset