TCI-W13, TCI-W23 Universal Controller 

O

PERATION

 

 

Doc: 70-00-0365, V1.0, 20200304 

© Vector Controls GmbH, Switzerland 

Page 2 

Subject to alteration 

Technical specifications 

Warning! 

This device is intended to be used for comfort applications. Where a device failure endangers human life and/or 

property, it is the responsibility of the owner, designer and installer to add additional safety devices to prevent or detect a 

system failure caused by such a device failure. The manufacturer of this device cannot be held liable for any damage 

caused by such a failure.  
Failure to follow specifications and local regulations may endanger life, cause equipment damage and void warranty. 

Power Supply 

Power Requirements  

24 VAC ±10%, 50/60 Hz,

 

Class 2, 2.0 A, 48 VA max. 

24 VDC ±10%

 

 

Power Consumption 

max. 3 VA 

 

Electrical Connection 

Terminal Connectors 

0.34…2.5 mm

2

 wire (AWG 22

…1

3)

 

 

Clock backup 

min. 48 hours 

Signal inputs 

Universal Input 
Input Signal 
Resolution 
Impedance 

Setting for voltage or current 
0

10 V or 0

20 mA 

9.76 mV or 0.019 mA (10 bit) 
Voltage: 98 

kΩ

 

Current: 240 

 

 

Universal Input 

Input configured to remote temperature (RT) or digital input (DI) 

Range 

NTC (Sxx-Tn10 sensor): -

40…140 

°C (-

40…284 °F)

 

Accuracy 

-

40…0 °C (

-

40…32 °F): 0.5 K

 

0…50 °C (32…122 °F): 0.2 K

 

50…100 °C (122…212 °F): 0.5 K

 

> 100 °C (> 212 °F): 1 K 

Humidity Sensor AES3-HT-Ax: 
Range 
Measuring Accuracy 
Hysteresis 
Repeatability 
Stability 

Capacity sensor  

0…100 % rH

 

See Figure to the right 

 1% 

 0.1% 

< 0.5% / year 

 

Signal outputs 

Analog output 
Output signal 
Resolution 
Maximum load 

 
DC 0

10 V / 0

20 mA 

9.76 mV / 0.019 mA 
Voltage: 

 5 

kΩ

 

Current: 

 250 

 

 

Relays outputs 
Type of disconnection  
AC voltage 
DC voltage 

 
Micro-interruption 

0…

48 VAC, 2(1.2) A max. (Observe local regulation)  

0…30 VDC, 2

 A max.  

 

Insulation strength 
between relays contacts and system 
electronics 

 
 
2000 VAC to EN 60730-1 

Environment 

Operation 
Climatic conditions 
Temperature 
Humidity 

To IEC 721-3-3 
class 3K5 

0…50 °C (32…122 °F)

 

< 95% RH non-condensing 

 

Transport & storage 
Climatic conditions 
Temperature 
Humidity 
Mechanical conditions 

To IEC 721-3-2 and IEC 721-3-1 
class 3K3 and class 1K3 
-25

…7

0 °C (-13

…158 °F)

 

< 95% RH non-condensing 
class 2M2 

Standards 

Degree of protection 

IP30 to EN 60529 

 

Pollution class 

II (EN 60730-1) 

 

Safety class 

III (IEC60536) 

 

Overvoltage category 

I (EN60730-1) 

General 

Material:  

Cover, back part 

 

Mounting plate 

Fire proof ABS plastic (UL94 class V-0) 
Galvanized steel 

 

Dimension (H x W x D) 

Front part: 21 x 88 x 88 mm (0.8 x 3.5 x 3.5 in.)  

Power case: ø 58 x 32 mm (ø 2.3” x 1.3”)

 

 

RoHS compliant according to 

2011/65/EU 

 

Weight (including package) 

TCI-W13 = 253 g (8.9 oz), TCI-W23 = 262 g (9.3 oz) 

 

 

Figure 1: Max RH-tolerance at 25°C (77°F) 

per sensor type 

Relative humidity accuracy 

 %RH 

 %RH 

10  20  30  40 

100 

90 

50  60  70  80 

±1 
±0 

±2 

±3 

±4 

±5 

AES3-HT-A2 

AES3-HT-A3 

AES3-HT-A5 

Содержание TCI-W13-H

Страница 1: ...s 1 internal temperature sensor 1 universal input 1 passive input 1 binary output 2 analog outputs Internal temperature sensor standard Add replaceable humidity element as required or order H version...

Страница 2: ...C 212 F 1 K Humidity Sensor AES3 HT Ax Range Measuring Accuracy Hysteresis Repeatability Stability Capacity sensor 0 100 rH See Figure to the right 1 0 1 0 5 year Signal outputs Analog output Output s...

Страница 3: ...or other devices Connection to voltages exceeding 42 V endangers personnel safety 88 3 5 32 1 2 21 0 8 88 3 5 Warning Live electrical components During installation testing servicing and troubleshoot...

Страница 4: ...e memorized and do not need to be re entered Upon return of power Set parameter UP05 to keep the unit off switch on or operation mode before power failure Clock and time schedule settings retained for...

Страница 5: ...yed clock symbol blinks Press OPTION Time schedule status displayed OFF or ON Press OPTION OFF ON blinks UP DOWN to change OPTION to save SEL PRO Pro OFF ON Creating time schedules Step 1 Select a swi...

Страница 6: ...onfiguration AO1 AO2 2 analog outputs DO Binary output configuration do1 1 binary digital outputs relays FU Special functions Common to all TCI How to change parameters 1 Press UP DOWN buttons simulta...

Страница 7: ...FF OFF Celsius UP 08 Show standard display while no key is pressed ON OFF ON UP 09 Select type of content for large digits 00 OFF 0 5 1 01 Input 02 Set point 03 Analog output 04 Binary output 05 Clock...

Страница 8: ...passive temperature NTC or dry contact Match sensor range to input display With a differential pressure transmitter having 0 200 Pa measuring range set UO1 display minimum to 0 and U02 display maximum...

Страница 9: ...limit in heating mode and maximum set point limit in cooling Economy mode may be disabled by setting UP06 to OFF Control loops and sequences are activated when output parameters are defined Cascade co...

Страница 10: ...This is the working range of the proportional control sequence Setting the proportional band to 0 disables proportional control Integral and differential control Proportional control is in most cases...

Страница 11: ...C 1 0 F 1L 22 Switching delay 0 255 s 10 s 1L 23 Activation of reverse direct heat cool sequence OFF activates based on demand ON follows heat cool state of controller Set manually or by auxiliary fun...

Страница 12: ...0 10 VDC default or 0 20 mA Further define analog outputs with A02 Custom ranges can be created by setting minimum and maximum signal limits A control loop special function digital control or analog c...

Страница 13: ...o set output to ON output OFF on conflicting alarms Alarm 1 2 3 4 5 6 7 8 ALA1 ALA8 1d 07 Choose alarm to set output to OFF output OFF on conflicting alarms Alarm 1 2 3 4 5 6 7 8 ALA1 ALA8 1d 08 Displ...

Страница 14: ...onds 0 1275 300 Fu 10 Input limit 1 per input 10 Fu 11 Input limit 2 Per input 90 Summer winter compensation changes the set point due to a change in an input value typically but not limited to an out...

Страница 15: ...mit 2 ON When limit 2 is greater than limit 1 enable when input value is between limit 1 and limit 2 When limit 2 is less than limit 1 enable when input value below limit 2 or above limit 1 ON OFF OFF...

Страница 16: ...mperature we recommend switching to cooling at 28 C 83 F and to heating at 16 C 61 F outdoor temperature These recommendations are given as suggestions The ideal settings may be different on the actua...

Страница 17: ...0 00 0365 V1 0 20200304 Vector Controls GmbH Switzerland Page 17 Subject to alteration Smart Sensors and Controls Made Easy Quality Innovation Partnership Vector Controls GmbH Switzerland info vectorc...

Отзывы: