TCI-W13, TCI-W23 Universal Controller 

I

NPUT 

C

ONFIGURATION

 

 

Doc: 70-00-0365, V1.0, 20200304 

© Vector Controls GmbH, Switzerland 

Page 8 

Subject to alteration 

Control configuration (Password 241) 

Input configuration 

Internal inputs 1T temperature, 1H humidity for 

H devices or with AES-HT inserted 

Parameter 

Description 

Range 

Default 

1T 00 

1H 00  Enable sensor 

OFF/ON 

ON 

1T 01 

1H 01  Display minimum value 

-50...205 

1T 02 

1H 02  Display maximum value 

-50...205 

100 

1T 03 

1H 03  Sensor sampling rate (control speed decrease as rate increases) 

0...100 

10 

1T 04 

1H 04  Sensor calibration 

per input 

1T 05 

1H 05  Low limit: Alarm 1 (1T), alarm 3 (1H), alarm 7 (2T) 

OFF/ON 

OFF 

1T 06 

1H 06  Alarm 1/3 low limit values 

-40...215 °C 

5 °C / 5% 

1T 07 

1H 07  High limit: Alarm 2 (1T), alarm (1H), alarm 8 (2T) 

OFF/ON 

OFF 

1T 08 

1H 08  Alarm 2/4 high limit values 

-40...215 °C 

50 °C / 95% 

1T 09 

1H 09  Hysteresis alarm 1, 2, 3, 4, 7, 8  

0...100 °C 

5 °C / 5% 

1T 10 

1H 10  Calculate a range of inputs (0 = not active):  

1 = average,  2 = minimum,  3 = maximum,  4 = differential 

0...3 

Universal input 1U, external passive input 2T for TCI-W23 

1U 00 

2T 00 

Signal type (0= not active): 

1 = 0...10 V or 0...20 mA or open contact, 2 = 2...10 V or 4...20 mA,  

3 = NTC temperature sensor 

0...3 

1U 01 

2T 01  Display minimum value 

-50...205 

1U 02 

2T 02  Display maximum value 

-50...205 

100 

1U 03 

2T 03  Analog input display range:  

0 = x0.1,  1 = x1,  2 = x10,  3 = x100 

0...3 

1U 04 

2T 04  Analog input unit of measure:   

0 = no unit,  1 = %,  2 = °C/°F,  3 = Pa 

0...3 

1U 05 

2T 05  Sensor sampling rate (control speed decrease as rate increases) 

0...100 

10 

1U 06 

2T 06  Sensor calibration  

Per input

 

1U 07 

2T 07  Alarm 5 low limit (1u), alarm 7 low limit (2t) 

OFF/ON 

OFF 

1U 08 

2T 08  Alarm 5 low limit value (1u), alarm 7 low limit value (2t) 

-40...215 °C 

5 °C (41 °F) 

1U 09 

2T 09  Alarm 6 high limit (1u), alarm 8 high limit (2t) 

OFF/ON 

OFF 

1U 10 

2T 10  Alarm 6 high limit value 1u), alarm 8 high limit value (2t) 

-40...215 °C 

50 °C 

(122 °F) 

1U 11 

2T 11  Hysteresis alarm 5 and 6 (1u), alarms 7 and 8 (2t) 

0...100 °C 

5 °C (10 °F) 

1U 12 

2T 12  Calculate a range of inputs (0 = not active):  

1 = average,  2 = minimum,  3 = maximum,  4 = differential 

0...4 

 

Set jumper for UI1 on the mounting plate: 0...10 VDC (default), 0...20 mA, or RT/DI (passive temperature NTC or 

dry contact) 

 

Match sensor range to input display. With a differential pressure transmitter having 0...200 Pa measuring range set 

UO1 display minimum to 0 and U02 display maximum to 200. The allowable range value of -50...205 may be 

adjusted with multipliers in U03. The largest displayable values are -990...9999. Limiting range increases resolution. 

Applies to analog as well as passive temperature inputs. 

 

For binary input (dry contact) set the jumper and parameter to RT/DI and change unit to % (1U04 = 1).  An open 

contact reads as a high value (100%), a closed contact as a low value (0%).  

 

Enable / Disable an alarm. Setting the alarm enable to OFF will prevent the alarm from being displayed on screen. It 

may never the less be used to control an output by setting the appropriate output alarm flags. This way, an alarm 

limit may be used as interlock.  

 

Specify the input value that triggers an alarm. Hysteresis is the difference between alarm level input and value 

required to turn the alarm off. An alarm is displayed as text if enabled (see table). Alarm text can be set to blink 

continuously until acknowledged by pressing the OPTION button or only while the alarm conditions are active (see 

user parameter UP15).  

 

Calculate mathematical functions over multiple inputs for loop control or display with xU12. In order to calculate 

average, minimum or maximum between several inputs, make sure all the inputs are of identical type and range and 

then activate the same function on xU12 on all the selected inputs. The largest input of the group selected will carry 

the calculated value. For example: When average is activated on 2T12 and 1U12 = 1, the average is carried on UI2. 

UI2 may now be used as input for control loops and it will show the average value of UI1 and TI2 combined. It is 

possible to use different functions on different inputs.  

 

The differential function may only be calculated on subsequent inputs. Such as TI2-UI1. The function must only be 

activated on the minuend (TI2 in this example). The displayed value of the minuend will change into the difference: 

TI2 in 

 UI1 = TI2 out. It is possible to have multiple differentials on one controller. It is not possible to reverse the 

subtraction to UI1-TI2. 

Input 

1T 

1H 

1U 

2T 

Low limit 

ALA1 

ALA3 

ALA5 

ALA7 

High limit 

ALA2 

ALA4 

ALA6 

ALA8 

Содержание TCI-W13-H

Страница 1: ...s 1 internal temperature sensor 1 universal input 1 passive input 1 binary output 2 analog outputs Internal temperature sensor standard Add replaceable humidity element as required or order H version...

Страница 2: ...C 212 F 1 K Humidity Sensor AES3 HT Ax Range Measuring Accuracy Hysteresis Repeatability Stability Capacity sensor 0 100 rH See Figure to the right 1 0 1 0 5 year Signal outputs Analog output Output s...

Страница 3: ...or other devices Connection to voltages exceeding 42 V endangers personnel safety 88 3 5 32 1 2 21 0 8 88 3 5 Warning Live electrical components During installation testing servicing and troubleshoot...

Страница 4: ...e memorized and do not need to be re entered Upon return of power Set parameter UP05 to keep the unit off switch on or operation mode before power failure Clock and time schedule settings retained for...

Страница 5: ...yed clock symbol blinks Press OPTION Time schedule status displayed OFF or ON Press OPTION OFF ON blinks UP DOWN to change OPTION to save SEL PRO Pro OFF ON Creating time schedules Step 1 Select a swi...

Страница 6: ...onfiguration AO1 AO2 2 analog outputs DO Binary output configuration do1 1 binary digital outputs relays FU Special functions Common to all TCI How to change parameters 1 Press UP DOWN buttons simulta...

Страница 7: ...FF OFF Celsius UP 08 Show standard display while no key is pressed ON OFF ON UP 09 Select type of content for large digits 00 OFF 0 5 1 01 Input 02 Set point 03 Analog output 04 Binary output 05 Clock...

Страница 8: ...passive temperature NTC or dry contact Match sensor range to input display With a differential pressure transmitter having 0 200 Pa measuring range set UO1 display minimum to 0 and U02 display maximum...

Страница 9: ...limit in heating mode and maximum set point limit in cooling Economy mode may be disabled by setting UP06 to OFF Control loops and sequences are activated when output parameters are defined Cascade co...

Страница 10: ...This is the working range of the proportional control sequence Setting the proportional band to 0 disables proportional control Integral and differential control Proportional control is in most cases...

Страница 11: ...C 1 0 F 1L 22 Switching delay 0 255 s 10 s 1L 23 Activation of reverse direct heat cool sequence OFF activates based on demand ON follows heat cool state of controller Set manually or by auxiliary fun...

Страница 12: ...0 10 VDC default or 0 20 mA Further define analog outputs with A02 Custom ranges can be created by setting minimum and maximum signal limits A control loop special function digital control or analog c...

Страница 13: ...o set output to ON output OFF on conflicting alarms Alarm 1 2 3 4 5 6 7 8 ALA1 ALA8 1d 07 Choose alarm to set output to OFF output OFF on conflicting alarms Alarm 1 2 3 4 5 6 7 8 ALA1 ALA8 1d 08 Displ...

Страница 14: ...onds 0 1275 300 Fu 10 Input limit 1 per input 10 Fu 11 Input limit 2 Per input 90 Summer winter compensation changes the set point due to a change in an input value typically but not limited to an out...

Страница 15: ...mit 2 ON When limit 2 is greater than limit 1 enable when input value is between limit 1 and limit 2 When limit 2 is less than limit 1 enable when input value below limit 2 or above limit 1 ON OFF OFF...

Страница 16: ...mperature we recommend switching to cooling at 28 C 83 F and to heating at 16 C 61 F outdoor temperature These recommendations are given as suggestions The ideal settings may be different on the actua...

Страница 17: ...0 00 0365 V1 0 20200304 Vector Controls GmbH Switzerland Page 17 Subject to alteration Smart Sensors and Controls Made Easy Quality Innovation Partnership Vector Controls GmbH Switzerland info vectorc...

Отзывы: