TCI-W13, TCI-W23 Universal Controller 

C

ONTROL LOOP 

C

ONFIGURATION

 

 

Doc: 70-00-0365, V1.0, 20200304 

© Vector Controls GmbH, Switzerland 

Page 11 

Subject to alteration 

Legend 

T, U

 

Input signal 

O

SH

 

Offset heating/direct

 

 

O

SC

 

Offset cooling/reverse

 

 

X

DZ

 

Dead zone 

X

SBY

 

Economy set point shift

 

W

H

 

Set point heating/reverse

  

W

C

 

Set point cooling/direct

 

Q

C

, Q

D

   

Binary sequences cooling/direct 

Q

H

, Q

R

   

Binary sequences heating/reverse 

Digital control sequence 

Parameter  Description 

Range 

Default 

1L 16 

Action of stages: 

0 = cumulative: stage 1 stays on when 2 on comes on 

1 = single: stage 1 turns off when 2 on comes on 

2 = digital: stage 1 only, stage 2 only, then stage 1 plus 2  

0...2 

1L 17 

Offset for heating/reverse binary sequences 

per input 

0.0 °C 

(0.0 °F) 

1L 18 

Offset for cooling/direct binary sequences 

per input 

0.0 °C 

(0.0 °F) 

1L 19 

Switching span heating 

per input 

1.0 °C 

(2.0 °F) 

1L 20 

Switching span cooling 

per input 

1.0 °C 

(2.0 °F) 

1L 21 

Switching hysteresis  

per input 

0.5 °C 

(1.0 °F) 

1L 22 

Switching delay  

0...255 s 

10 s 

1L 23 

Activation of reverse/direct (heat/cool) sequence 

OFF = activates based on demand 

ON  = follows heat/cool state of controller: Set manually or by 

auxiliary function (FU20...FU23) 

ON/OFF 

OFF 

1L 24 

Delay for heat /cool changeover when L23=OFF 

0...255 min 

5 min 

 

 

Cumulative stage action (L16 = 0) is typically used in electric heat applications, and single stage action (L16 = 1) in 

fan speed applications. Digital stage action (L16 = 2) is especially useful in electric heat applications to generate 

three steps with just two outputs. For example: Step 1 = 100W, step 2 = 200W, step 3 = 300W.  

 

 

 

 

 

 

 

Switching hysteresis (L21) is the difference between switching on and switching off. A small hysteresis will increase 

the number of switching cycles and thus the wear on associated equipment.  

 

With switching delay (L22) cumulative stages will not switch on simultaneously. With a sudden demand or initial 

power stage 2 will not start earlier than 10 seconds (default value) after stage 1 has been initiated.  

 

 

 

Cumulative  

Single  

Digital  

Stage 1 

Q

1

 

Q

1

 

Q

1

 

Stage 2 

Q

1

+Q

2

 

Q

2

 

Q

2

 

Stage 3 

 

 

Q

1

+Q

2

 

ON 

OFF 

T [°C, °F] 
U [V, mA] 
 

Q

C2, 

Q

D2

 

O

SH

 

W

O

SC

 

X

DZ

 

W

X

H

 

Q

C1, 

Q

D1

 

Q

H2, 

Q

R2

 

 

Содержание TCI-W13-H

Страница 1: ...s 1 internal temperature sensor 1 universal input 1 passive input 1 binary output 2 analog outputs Internal temperature sensor standard Add replaceable humidity element as required or order H version...

Страница 2: ...C 212 F 1 K Humidity Sensor AES3 HT Ax Range Measuring Accuracy Hysteresis Repeatability Stability Capacity sensor 0 100 rH See Figure to the right 1 0 1 0 5 year Signal outputs Analog output Output s...

Страница 3: ...or other devices Connection to voltages exceeding 42 V endangers personnel safety 88 3 5 32 1 2 21 0 8 88 3 5 Warning Live electrical components During installation testing servicing and troubleshoot...

Страница 4: ...e memorized and do not need to be re entered Upon return of power Set parameter UP05 to keep the unit off switch on or operation mode before power failure Clock and time schedule settings retained for...

Страница 5: ...yed clock symbol blinks Press OPTION Time schedule status displayed OFF or ON Press OPTION OFF ON blinks UP DOWN to change OPTION to save SEL PRO Pro OFF ON Creating time schedules Step 1 Select a swi...

Страница 6: ...onfiguration AO1 AO2 2 analog outputs DO Binary output configuration do1 1 binary digital outputs relays FU Special functions Common to all TCI How to change parameters 1 Press UP DOWN buttons simulta...

Страница 7: ...FF OFF Celsius UP 08 Show standard display while no key is pressed ON OFF ON UP 09 Select type of content for large digits 00 OFF 0 5 1 01 Input 02 Set point 03 Analog output 04 Binary output 05 Clock...

Страница 8: ...passive temperature NTC or dry contact Match sensor range to input display With a differential pressure transmitter having 0 200 Pa measuring range set UO1 display minimum to 0 and U02 display maximum...

Страница 9: ...limit in heating mode and maximum set point limit in cooling Economy mode may be disabled by setting UP06 to OFF Control loops and sequences are activated when output parameters are defined Cascade co...

Страница 10: ...This is the working range of the proportional control sequence Setting the proportional band to 0 disables proportional control Integral and differential control Proportional control is in most cases...

Страница 11: ...C 1 0 F 1L 22 Switching delay 0 255 s 10 s 1L 23 Activation of reverse direct heat cool sequence OFF activates based on demand ON follows heat cool state of controller Set manually or by auxiliary fun...

Страница 12: ...0 10 VDC default or 0 20 mA Further define analog outputs with A02 Custom ranges can be created by setting minimum and maximum signal limits A control loop special function digital control or analog c...

Страница 13: ...o set output to ON output OFF on conflicting alarms Alarm 1 2 3 4 5 6 7 8 ALA1 ALA8 1d 07 Choose alarm to set output to OFF output OFF on conflicting alarms Alarm 1 2 3 4 5 6 7 8 ALA1 ALA8 1d 08 Displ...

Страница 14: ...onds 0 1275 300 Fu 10 Input limit 1 per input 10 Fu 11 Input limit 2 Per input 90 Summer winter compensation changes the set point due to a change in an input value typically but not limited to an out...

Страница 15: ...mit 2 ON When limit 2 is greater than limit 1 enable when input value is between limit 1 and limit 2 When limit 2 is less than limit 1 enable when input value below limit 2 or above limit 1 ON OFF OFF...

Страница 16: ...mperature we recommend switching to cooling at 28 C 83 F and to heating at 16 C 61 F outdoor temperature These recommendations are given as suggestions The ideal settings may be different on the actua...

Страница 17: ...0 00 0365 V1 0 20200304 Vector Controls GmbH Switzerland Page 17 Subject to alteration Smart Sensors and Controls Made Easy Quality Innovation Partnership Vector Controls GmbH Switzerland info vectorc...

Отзывы: