TCI-W13, TCI-W23 Universal Controller 

O

PERATION

 

 

Doc: 70-00-0365, V1.0, 20200304 

© Vector Controls GmbH, Switzerland 

Page 3 

Subject to alteration 

Dimensions, mm (inch) and Installation 

  

Connection  

 

Terminal Description  

G0 

Power supply:  

0 V, -24 VDC; common for power supply, analog in- and outputs 

Power supply:  

24 VAC, +24 VDC 

X

U1

 

Universal input: 

NTC 10 k

Ω @ 25

 °C (77 °F) or open contact

, 0…10

 VDC 

or 0…20 mA

  

 

 

 

(selectable by jumper) 

X

T2

 

Passive input:  

NTC 10 k

Ω @ 25

 °C (77 °F) or open contact 

Y

B1

 

Binary output:

 

Potential free relays contacts (see technical specification)

 

Y

M1, 

X

M2

 Analog outputs:  

0…10 V or 0…20 mA

X

T1

 

Internal temperature input 

X

H1

 

Internal humidity input if AES3-HT is inserted 

 

Use copper, twisted pair, conductors only. The operating voltage must comply with the requirements for safety extra-low 

voltage (SELV) as per EN 60730. Use safety insulating transformers class II with double insulation as per EN 60742; they 

must be designed for 100% ON-time. When using several transformers in one system, the connection terminal 1 must be 

galvanic connected. TCI is designed for operation of 24 VAC safety extra-low voltage and is short-circuit-proof. Supplying 

voltages above 24 VAC to low voltage connections may damage the controller or other devices. Connection to voltages 
exceeding 42 V endangers personnel safety. 

88 (3.5) 

32 (1.2) 

21  

(0.8) 

8

8

 (

3

.5

Warning

:  

Live electrical components! 

During installation, testing, servicing 
and troubleshooting of Vector 
Controls products, it may be 
necessary to work with live electrical 
components. Have a qualified 
licensed electrician or other 
individual who has been properly 
trained in handling live electrical 
components perform these tasks. 
Failure to follow all electrical safety 

precautions when exposed to live 
electrical components could result in 
death or serious injury.

 

X

H1 

X

T1 

0 V (COM) 

24 V AC/DC 
 

TCI-W13 

G0 

0…48 VAC, 0…30 VDC

 


Q13 

1    5  

G0   Y1 

Y

M1

 

  1       7 
  G0    X1 

X

U1 

Y

B1

 

Q14      

0 VAC 

1    6  

G0   Y2 

Y

M2

 

  1       8 
  G0    X2 

X

H1 

X

T1 

0 V (COM) 

24 V AC/DC 
 

TCI-W23 

G0 

0...48 VAC, 0…30 VDC

 


Q13 

1    5  

G0   Y1 

Y

M1

 

  1       7 
  G0    X1 

X

U1 

Y

B1

 

Q14      

0 V AC 

X

T2 

1    6  

G0   Y2 

Y

M2

 

 

Install the controller on an easy accessible 

interior wall, approx. 1.5 m above the floor 

in an area of average temperature. 

 

Avoid direct sunlight or other heat sources, 

e.g. the area above radiators and heat 

emitting equipment.  

 

Avoid locations behind doors, outside walls 

and below or above air discharge grills and 

diffusers.  

 

Location of mounting is less critical if 

external temperature sensors are used. 

 

Ensure adequate air circulation to dissipate 

heat generated during operation. 

 

Observe local regulations. 
Do not mount in a wet or condensation 

prone environments. 

Содержание TCI-W13-H

Страница 1: ...s 1 internal temperature sensor 1 universal input 1 passive input 1 binary output 2 analog outputs Internal temperature sensor standard Add replaceable humidity element as required or order H version...

Страница 2: ...C 212 F 1 K Humidity Sensor AES3 HT Ax Range Measuring Accuracy Hysteresis Repeatability Stability Capacity sensor 0 100 rH See Figure to the right 1 0 1 0 5 year Signal outputs Analog output Output s...

Страница 3: ...or other devices Connection to voltages exceeding 42 V endangers personnel safety 88 3 5 32 1 2 21 0 8 88 3 5 Warning Live electrical components During installation testing servicing and troubleshoot...

Страница 4: ...e memorized and do not need to be re entered Upon return of power Set parameter UP05 to keep the unit off switch on or operation mode before power failure Clock and time schedule settings retained for...

Страница 5: ...yed clock symbol blinks Press OPTION Time schedule status displayed OFF or ON Press OPTION OFF ON blinks UP DOWN to change OPTION to save SEL PRO Pro OFF ON Creating time schedules Step 1 Select a swi...

Страница 6: ...onfiguration AO1 AO2 2 analog outputs DO Binary output configuration do1 1 binary digital outputs relays FU Special functions Common to all TCI How to change parameters 1 Press UP DOWN buttons simulta...

Страница 7: ...FF OFF Celsius UP 08 Show standard display while no key is pressed ON OFF ON UP 09 Select type of content for large digits 00 OFF 0 5 1 01 Input 02 Set point 03 Analog output 04 Binary output 05 Clock...

Страница 8: ...passive temperature NTC or dry contact Match sensor range to input display With a differential pressure transmitter having 0 200 Pa measuring range set UO1 display minimum to 0 and U02 display maximum...

Страница 9: ...limit in heating mode and maximum set point limit in cooling Economy mode may be disabled by setting UP06 to OFF Control loops and sequences are activated when output parameters are defined Cascade co...

Страница 10: ...This is the working range of the proportional control sequence Setting the proportional band to 0 disables proportional control Integral and differential control Proportional control is in most cases...

Страница 11: ...C 1 0 F 1L 22 Switching delay 0 255 s 10 s 1L 23 Activation of reverse direct heat cool sequence OFF activates based on demand ON follows heat cool state of controller Set manually or by auxiliary fun...

Страница 12: ...0 10 VDC default or 0 20 mA Further define analog outputs with A02 Custom ranges can be created by setting minimum and maximum signal limits A control loop special function digital control or analog c...

Страница 13: ...o set output to ON output OFF on conflicting alarms Alarm 1 2 3 4 5 6 7 8 ALA1 ALA8 1d 07 Choose alarm to set output to OFF output OFF on conflicting alarms Alarm 1 2 3 4 5 6 7 8 ALA1 ALA8 1d 08 Displ...

Страница 14: ...onds 0 1275 300 Fu 10 Input limit 1 per input 10 Fu 11 Input limit 2 Per input 90 Summer winter compensation changes the set point due to a change in an input value typically but not limited to an out...

Страница 15: ...mit 2 ON When limit 2 is greater than limit 1 enable when input value is between limit 1 and limit 2 When limit 2 is less than limit 1 enable when input value below limit 2 or above limit 1 ON OFF OFF...

Страница 16: ...mperature we recommend switching to cooling at 28 C 83 F and to heating at 16 C 61 F outdoor temperature These recommendations are given as suggestions The ideal settings may be different on the actua...