TCI-W13, TCI-W23 Universal Controller 

S

ETUP AND 

C

ONFIGURATION

 

 

Doc: 70-00-0365, V1.0, 20200304 

© Vector Controls GmbH, Switzerland 

Page 6 

Subject to alteration 

Setting parameters to configure the controller 

TCI is an intelligent

 

controller with the flexibility to fit a wide range of applications. The control operation is defined by 

parameters set using the standard operation terminal. There are two levels: 

1.

 

User/display parameters (password 0009) 

2.

 

Control parameters (password 00241)  

Recommended set-up procedure: 

1.

 

Set jumpers on the back of the controller for inputs and outputs 

2.

 

Connect power supply and inputs 

3.

 

Make sure Celsius 

 Fahrenheit settings are correct (UP07) 

4.

 

Program input parameters  

5.

 

Program control parameters 

6.

 

Program output parameters 

7.

 

Program auxiliary functions and user settings 

8.

 

Test function of unit 

9.

 

Switch off power 

10.

 

Connect outputs 

11.

 

Test control loop 

Parameters are grouped according to modules: 

 

Module 

Description 

Notes 

PW 

UP 

User and display parameters 

Control user access and select display elements, 
regional settings 

009 

UI 

Input configuration: 1T, 1H, 1U, 2T 

TCI-W23: Internal temp. and RH, 2 universal inputs 
TCI-W13: Internal temp. 1 universal input 

241 

LP 

Control loops Lp1, Lp2 

TCI-W23: 2 independent control loops 
TCI-W13: 1 independent control loop 

AO 

Analog output configuration, AO1, AO2 

2 analog outputs 

DO 

Binary output configuration, do1 

1 binary (digital) outputs - relays 

FU 

Special functions 

Common to all TCI 

 

How to change parameters 

1.

 

Press UP/DOWN buttons simultaneously for three seconds. The display will show firmware version and revision 

number. Press the OPTION button to start login 

2.

 

CODE is shown in small display 

3.

 

Code to access user parameters is 009, control parameter is 241. The access numbers are fixed and cannot be 

changed 

4.

 

Select this using UP/DOWN buttons 

5.

 

Press OPTION after selecting the correct code  

6.

 

Once logged in with 009, the user/display parameters are displayed immediately. Once logged in with 241 control 

modules are displayed (Lp1, Lp2, 1u, 2t, etc.) 

 select with UP/DOWN and open with OPTION. As soon as the module 

is open its parameters are displayed 

7.

 

Select the parameters with the UP/DOWN buttons. Change a parameter by pressing the OPTION button. Three arrows 

are displayed to indicate that the parameter may be modified. Use UP/DOWN buttons to adjust the value 

8.

 

After you are done, press OPTION to save the new value and return to the selection level (arrows disappear when 

selection is saved). Pressing left hand POWER button without pressing OPTION will discard the value and return 

without saving. For control parameters press POWER again to leave parameter selection and return to control module 

selection 

9.

 

Press the POWER to leave the menu. The unit will return to normal operation if no button is pressed for more than 5 

minutes

Содержание TCI-W13-H

Страница 1: ...s 1 internal temperature sensor 1 universal input 1 passive input 1 binary output 2 analog outputs Internal temperature sensor standard Add replaceable humidity element as required or order H version...

Страница 2: ...C 212 F 1 K Humidity Sensor AES3 HT Ax Range Measuring Accuracy Hysteresis Repeatability Stability Capacity sensor 0 100 rH See Figure to the right 1 0 1 0 5 year Signal outputs Analog output Output s...

Страница 3: ...or other devices Connection to voltages exceeding 42 V endangers personnel safety 88 3 5 32 1 2 21 0 8 88 3 5 Warning Live electrical components During installation testing servicing and troubleshoot...

Страница 4: ...e memorized and do not need to be re entered Upon return of power Set parameter UP05 to keep the unit off switch on or operation mode before power failure Clock and time schedule settings retained for...

Страница 5: ...yed clock symbol blinks Press OPTION Time schedule status displayed OFF or ON Press OPTION OFF ON blinks UP DOWN to change OPTION to save SEL PRO Pro OFF ON Creating time schedules Step 1 Select a swi...

Страница 6: ...onfiguration AO1 AO2 2 analog outputs DO Binary output configuration do1 1 binary digital outputs relays FU Special functions Common to all TCI How to change parameters 1 Press UP DOWN buttons simulta...

Страница 7: ...FF OFF Celsius UP 08 Show standard display while no key is pressed ON OFF ON UP 09 Select type of content for large digits 00 OFF 0 5 1 01 Input 02 Set point 03 Analog output 04 Binary output 05 Clock...

Страница 8: ...passive temperature NTC or dry contact Match sensor range to input display With a differential pressure transmitter having 0 200 Pa measuring range set UO1 display minimum to 0 and U02 display maximum...

Страница 9: ...limit in heating mode and maximum set point limit in cooling Economy mode may be disabled by setting UP06 to OFF Control loops and sequences are activated when output parameters are defined Cascade co...

Страница 10: ...This is the working range of the proportional control sequence Setting the proportional band to 0 disables proportional control Integral and differential control Proportional control is in most cases...

Страница 11: ...C 1 0 F 1L 22 Switching delay 0 255 s 10 s 1L 23 Activation of reverse direct heat cool sequence OFF activates based on demand ON follows heat cool state of controller Set manually or by auxiliary fun...

Страница 12: ...0 10 VDC default or 0 20 mA Further define analog outputs with A02 Custom ranges can be created by setting minimum and maximum signal limits A control loop special function digital control or analog c...

Страница 13: ...o set output to ON output OFF on conflicting alarms Alarm 1 2 3 4 5 6 7 8 ALA1 ALA8 1d 07 Choose alarm to set output to OFF output OFF on conflicting alarms Alarm 1 2 3 4 5 6 7 8 ALA1 ALA8 1d 08 Displ...

Страница 14: ...onds 0 1275 300 Fu 10 Input limit 1 per input 10 Fu 11 Input limit 2 Per input 90 Summer winter compensation changes the set point due to a change in an input value typically but not limited to an out...

Страница 15: ...mit 2 ON When limit 2 is greater than limit 1 enable when input value is between limit 1 and limit 2 When limit 2 is less than limit 1 enable when input value below limit 2 or above limit 1 ON OFF OFF...

Страница 16: ...mperature we recommend switching to cooling at 28 C 83 F and to heating at 16 C 61 F outdoor temperature These recommendations are given as suggestions The ideal settings may be different on the actua...

Страница 17: ...0 00 0365 V1 0 20200304 Vector Controls GmbH Switzerland Page 17 Subject to alteration Smart Sensors and Controls Made Easy Quality Innovation Partnership Vector Controls GmbH Switzerland info vectorc...

Отзывы: