TCI-W13, TCI-W23 Universal Controller 

A

UX 

F

UNCTIONS 

C

ONFIGURATION

 

 

Doc: 70-00-0365, V1.0, 20200304 

© Vector Controls GmbH, Switzerland 

Page 16 

Subject to alteration 

Heating/cooling mode changeover 

Parameter  Description 

Range 

Default 

Fu 20 

Select heat/cool changeover input (0 = function disabled):  
1 = 1T,  2 = 1H,  3 = 1U,  4 = 2T,  5 = h/c status loop 1,   

6 = h/c status loop 2 

0...6 

Fu 21 

Cooling activation delay (seconds)  

0...1275 

300 

Fu 22 

Input limit 1 

per input 

20 

Fu 23 

Input limit 2 

per input 

40 

 

 

Switch heating/cooling state based on a universal input value. The input may be from a supply media (air or water) 

or outdoor air temperature sensor. For supply media temperature we recommend switching to cooling at 16 °C/61 °F 

and to heating at 28 °C/83 °F. For outdoor temperature we recommend switching to cooling at 28 °C/83 °F and to 

heating at 16 °C/61 °F outdoor temperature. These recommendations are given as suggestions. The ideal settings 

may be different on the actual project depending on climatic and system conditions.   

 

The change between heating and cooling is delayed to avoid unnecessary switching (FU21). Heat/cool status of one 

control loop may also be determined by the heat/cool state of the other loop (FU20= 5 or 6). The control loop used to 
determine the heat /cool state must be set to demand-based heating and cooling with (L23). Set limit 1 and limit 2 to 

switch between heating and cooling with options below. Example: When Limit 2 is greater than Limit 1, switch heat to 

cool at Limit 1, cool to heat at Limit 2. For binary open/close contact, open is a high value (100%), closed is a low 

value (0%). 

 

 

Cool 

Mode 

Mode 

Heat 

Input  

Limit 2 > Limit 1  

Heat 

Cool 

Input 

Limit 1 > Limit 2  

Limit  

Limit  

Limit  

Limit  

Содержание TCI-W13-H

Страница 1: ...s 1 internal temperature sensor 1 universal input 1 passive input 1 binary output 2 analog outputs Internal temperature sensor standard Add replaceable humidity element as required or order H version...

Страница 2: ...C 212 F 1 K Humidity Sensor AES3 HT Ax Range Measuring Accuracy Hysteresis Repeatability Stability Capacity sensor 0 100 rH See Figure to the right 1 0 1 0 5 year Signal outputs Analog output Output s...

Страница 3: ...or other devices Connection to voltages exceeding 42 V endangers personnel safety 88 3 5 32 1 2 21 0 8 88 3 5 Warning Live electrical components During installation testing servicing and troubleshoot...

Страница 4: ...e memorized and do not need to be re entered Upon return of power Set parameter UP05 to keep the unit off switch on or operation mode before power failure Clock and time schedule settings retained for...

Страница 5: ...yed clock symbol blinks Press OPTION Time schedule status displayed OFF or ON Press OPTION OFF ON blinks UP DOWN to change OPTION to save SEL PRO Pro OFF ON Creating time schedules Step 1 Select a swi...

Страница 6: ...onfiguration AO1 AO2 2 analog outputs DO Binary output configuration do1 1 binary digital outputs relays FU Special functions Common to all TCI How to change parameters 1 Press UP DOWN buttons simulta...

Страница 7: ...FF OFF Celsius UP 08 Show standard display while no key is pressed ON OFF ON UP 09 Select type of content for large digits 00 OFF 0 5 1 01 Input 02 Set point 03 Analog output 04 Binary output 05 Clock...

Страница 8: ...passive temperature NTC or dry contact Match sensor range to input display With a differential pressure transmitter having 0 200 Pa measuring range set UO1 display minimum to 0 and U02 display maximum...

Страница 9: ...limit in heating mode and maximum set point limit in cooling Economy mode may be disabled by setting UP06 to OFF Control loops and sequences are activated when output parameters are defined Cascade co...

Страница 10: ...This is the working range of the proportional control sequence Setting the proportional band to 0 disables proportional control Integral and differential control Proportional control is in most cases...

Страница 11: ...C 1 0 F 1L 22 Switching delay 0 255 s 10 s 1L 23 Activation of reverse direct heat cool sequence OFF activates based on demand ON follows heat cool state of controller Set manually or by auxiliary fun...

Страница 12: ...0 10 VDC default or 0 20 mA Further define analog outputs with A02 Custom ranges can be created by setting minimum and maximum signal limits A control loop special function digital control or analog c...

Страница 13: ...o set output to ON output OFF on conflicting alarms Alarm 1 2 3 4 5 6 7 8 ALA1 ALA8 1d 07 Choose alarm to set output to OFF output OFF on conflicting alarms Alarm 1 2 3 4 5 6 7 8 ALA1 ALA8 1d 08 Displ...

Страница 14: ...onds 0 1275 300 Fu 10 Input limit 1 per input 10 Fu 11 Input limit 2 Per input 90 Summer winter compensation changes the set point due to a change in an input value typically but not limited to an out...

Страница 15: ...mit 2 ON When limit 2 is greater than limit 1 enable when input value is between limit 1 and limit 2 When limit 2 is less than limit 1 enable when input value below limit 2 or above limit 1 ON OFF OFF...

Страница 16: ...mperature we recommend switching to cooling at 28 C 83 F and to heating at 16 C 61 F outdoor temperature These recommendations are given as suggestions The ideal settings may be different on the actua...

Страница 17: ...0 00 0365 V1 0 20200304 Vector Controls GmbH Switzerland Page 17 Subject to alteration Smart Sensors and Controls Made Easy Quality Innovation Partnership Vector Controls GmbH Switzerland info vectorc...

Отзывы: