TCI-W13, TCI-W23 Universal Controller 

O

UTPUT 

C

ONFIGURATION

 

 

Doc: 70-00-0365, V1.0, 20200304 

© Vector Controls GmbH, Switzerland 

Page 12 

Subject to alteration 

W

W

Y

H1

,Y

R1 

X

DZ

 

Y

C1,

Y

D1

 

Heating 

Cooling 

1A04

 

1A05

 

1A03

 

 1A06

 

T (°C/F), U(V, mA) 

100%

 

50%

 

0%

 

Output priority  

1. Alarm level low 
2. Alarm level high 

3. Operation mode OFF 
4. Control function 

Output configuration 

Analog output configuration (1A, 2A) 

Parameter  Description 

Range 

Default 

1A 00 

Select control loop or special function (0 = OFF): 

1 = LP1 

2 = LP2 

3 = Dehumidify (4 pipe, max LP1 cooling, LP2 direct) 

4 = Manual positioning or by time schedule (0...100%) 

5 = Transmit value of an input 

0...5 

1A 01 

When 1A00 = 1 configure output:

 

0 = Heating/reverse  

1 = Cooling/direct

 

2 = Heating and cooling (2 pipe)

 

3 = Transmit set point

 

When 1A00 = 4 Manual positioning or time schedule controlled 

0 = Time schedule only 
1 = Manual positioning and by time schedule 

When 1A00 = 5, select input (0 = function disabled): 

1 = 1T, 2 = 1H,  3 = 1U,  4 = 2T

 

0...4 

1A 02 

Type of output signal: OFF =  0...10 V, 0...20 mA,  ON= 2...10 V, 

4...20 mA 

ON/OFF 

OFF 

1A 03 

Minimum limitation of output signal default and in loop heating mode 

0...100% 

1A 04 

Maximum limitation of output signal default and in loop heating mode 

0...100% 

100% 

1A 05 

Minimum limitation of output signal in loop cooling mode 

0...100% 

0% 

1A 06 

Maximum limitation of output signal in loop cooling mode  

0...100% 

100% 

1A 07 

Choose alarm to set output to 100% (output 0% on conflicting alarms) 
  

 



 

Alarm:   1 2 3 4 5 6 7 8 

ALA1...ALA8 



 

1A 08 

Choose alarm to set output to 0% (output 0% on conflicting alarms) 
  

 



 

Alarm:   1 2 3 4 5 6 7 8 

ALA1...ALA8 



 

1A 09 

Transmit value (1A00 = 5): minimum input value 

per input 

0 °C 

1A 10 

Transmit value (1A00 = 5): maximum input value 

per input 

100 °C 

 

Set jumpers on the back of the controller: 0...10 VDC (default), or 0...20 mA. Further define analog outputs with A02. 

Custom ranges can be created by setting minimum and maximum signal limits. 

 

A control loop, special function, digital control or analog control sequence is not active until it is assigned an output.  

 

Low and high limit alarms are defined with input parameters. With output parameters assign an 

alarm to an output and select output state. The required output for each alarm can be 

individually selected. Multiple alarms can be signed to one output. If one alarm is selected to 

simultaneously activate and deactivate an output, the one to de-activate has precedence.  

 

With manual positioning (1A00 = 4) position the output by time schedule or directly in 0.5% 

steps. Setting 1A01 to 0 will disable manual positioning. The output will then only be controlled by time schedule.  

 

With dehumidifying (1A00 = 3) the maximum value is taken of cooling and dehumidifying. When the humidity is too 
high, cooling will continue to operate, even without a demand for cooling, to dehumidify the air and heating will 
activate to maintain comfort.  

 

Input

 

values of inputs and set points of control loops may be transmitted on the analog outputs. 

 

For 

VAV function

 individual minimum and 

maximum limits may be assigned for cooling 

and heating. In VAV applications maximum 

cooling output matches the maximum air 

volume the VAV box is set to deliver. As 

demand for airflow in cooling mode decreases, 

airflow dwindles until it reaches minimum 

cooling output (1A05). This minimum will be 

based on the airflow needed at design cooling 

and is typically 10% to 15% of maximum 

cooling airflow. When this minimum is 

reached the system is in dead-band 

 neither 

heating nor cooling. Minimum airflow in 

heating mode is set with 1A03. As the system 

moves into heating mode, heating airflow 

increases until it reaches the maximum 

heating output (1A04), typically 30 to 50% of 

maximum cooling airflow.   

 

 

 

Содержание TCI-W13-H

Страница 1: ...s 1 internal temperature sensor 1 universal input 1 passive input 1 binary output 2 analog outputs Internal temperature sensor standard Add replaceable humidity element as required or order H version...

Страница 2: ...C 212 F 1 K Humidity Sensor AES3 HT Ax Range Measuring Accuracy Hysteresis Repeatability Stability Capacity sensor 0 100 rH See Figure to the right 1 0 1 0 5 year Signal outputs Analog output Output s...

Страница 3: ...or other devices Connection to voltages exceeding 42 V endangers personnel safety 88 3 5 32 1 2 21 0 8 88 3 5 Warning Live electrical components During installation testing servicing and troubleshoot...

Страница 4: ...e memorized and do not need to be re entered Upon return of power Set parameter UP05 to keep the unit off switch on or operation mode before power failure Clock and time schedule settings retained for...

Страница 5: ...yed clock symbol blinks Press OPTION Time schedule status displayed OFF or ON Press OPTION OFF ON blinks UP DOWN to change OPTION to save SEL PRO Pro OFF ON Creating time schedules Step 1 Select a swi...

Страница 6: ...onfiguration AO1 AO2 2 analog outputs DO Binary output configuration do1 1 binary digital outputs relays FU Special functions Common to all TCI How to change parameters 1 Press UP DOWN buttons simulta...

Страница 7: ...FF OFF Celsius UP 08 Show standard display while no key is pressed ON OFF ON UP 09 Select type of content for large digits 00 OFF 0 5 1 01 Input 02 Set point 03 Analog output 04 Binary output 05 Clock...

Страница 8: ...passive temperature NTC or dry contact Match sensor range to input display With a differential pressure transmitter having 0 200 Pa measuring range set UO1 display minimum to 0 and U02 display maximum...

Страница 9: ...limit in heating mode and maximum set point limit in cooling Economy mode may be disabled by setting UP06 to OFF Control loops and sequences are activated when output parameters are defined Cascade co...

Страница 10: ...This is the working range of the proportional control sequence Setting the proportional band to 0 disables proportional control Integral and differential control Proportional control is in most cases...

Страница 11: ...C 1 0 F 1L 22 Switching delay 0 255 s 10 s 1L 23 Activation of reverse direct heat cool sequence OFF activates based on demand ON follows heat cool state of controller Set manually or by auxiliary fun...

Страница 12: ...0 10 VDC default or 0 20 mA Further define analog outputs with A02 Custom ranges can be created by setting minimum and maximum signal limits A control loop special function digital control or analog c...

Страница 13: ...o set output to ON output OFF on conflicting alarms Alarm 1 2 3 4 5 6 7 8 ALA1 ALA8 1d 07 Choose alarm to set output to OFF output OFF on conflicting alarms Alarm 1 2 3 4 5 6 7 8 ALA1 ALA8 1d 08 Displ...

Страница 14: ...onds 0 1275 300 Fu 10 Input limit 1 per input 10 Fu 11 Input limit 2 Per input 90 Summer winter compensation changes the set point due to a change in an input value typically but not limited to an out...

Страница 15: ...mit 2 ON When limit 2 is greater than limit 1 enable when input value is between limit 1 and limit 2 When limit 2 is less than limit 1 enable when input value below limit 2 or above limit 1 ON OFF OFF...

Страница 16: ...mperature we recommend switching to cooling at 28 C 83 F and to heating at 16 C 61 F outdoor temperature These recommendations are given as suggestions The ideal settings may be different on the actua...

Страница 17: ...0 00 0365 V1 0 20200304 Vector Controls GmbH Switzerland Page 17 Subject to alteration Smart Sensors and Controls Made Easy Quality Innovation Partnership Vector Controls GmbH Switzerland info vectorc...

Отзывы: