TCI-W13, TCI-W23 Universal Controller 

C

ONTROL LOOP 

C

ONFIGURATION

 

 

Doc: 70-00-0365, V1.0, 20200304 

© Vector Controls GmbH, Switzerland 

Page 10 

Subject to alteration 

Legend 

T, U 

Input signal temp/universal 

X

PH

 

P-band heating/direct 

 

X

PC

 

P-band cooling/reverse 

 

X

DZ

 

Dead zone h/c set points 

X

SBY

 

Economy mode set point shift 

W

H

 

Set point heating/reverse  

W

C

 

Set point cooling/direct 

Y

H1, 

Y

R1

  PI sequence heating/reverse 

Y

C1, 

Y

D1

  PI sequence cooling/direct 

 

PI control sequence 

Parameter  Description 

Range 

Default 

1L 09 

Offset for heating PI sequence 

per input 

1L 10 

Offset for cooling PI sequence 

per input 

1L 11 

P-band heating  

per input 

2.0 °C 

(4.0 °F) 

1L 12 

P-band cooling  

per input 

2.0 °C 

(4.0 °F) 

1L 13 

Integral gain heating (0.1 steps) 
Low = slow reaction,  high = fast reaction 

0...25.5 

0.0 

1L 14 

Integral gain cooling (0.1 steps) 

0...25.5 

0.0 

1L 15 

Measuring interval integral (seconds) 
Low = fast reaction, high value = slow reaction 

0...255 

 

Proportional control

 

(P-band)  

The proportional control function calculates the output based on the difference between set point and measured value. 

The proportional band (P-band) defines the difference between set point and measured value which will result in a 

100% output. For example, with a heating or reverse 0...10 V control sequence, and a 2.0 °C (4.0 °F) P-band value, 

at 10 V the controller will be 2.0 °C (4.0 °F) below set point. This is the working range of the proportional control 

sequence. 

Setting the proportional band to 0 disables proportional control. 

 

 

Integral and differential control

  

Proportional control is in most cases a very stable control mode. The flaw of proportional control alone, however, is 

that the set point is normally not reached. As the measured value gets closer to the set point, the output reduces 

until it reaches a point, a fraction above or below the set point, where the output equals the load. To reach the set 

point and achieve a higher level in comfort the integral/differential function should be activated.  

Integral gain (KI) 

dynamically increases the output by the selected KI value every 

measuring interval TI

 until 

the set point is reached. The challenge is to prevent hunting, where the output increases too fast, the temperature 

overshoots the set point, the output goes to 0, the temperature undershoots the set point, and the cycle repeats itself. 

Hunting may result if the integral gain

 

is too high or measuring interval too short. Each system is different. To 

prevent instability the P-band should be extended when integral gain is active (L14 or L15 set above 0).  

Setting the integral gain to 0 disables integral and differential control. 

 

 

 

 

 

Recommended values 

 

heating (air)  heating (radiant)

 

humidifying

 

cooling 

dehumidifying

 

pressure 

 

P-band 

2...3 °C (4...6 °F) 

1...1.5 °C (2...3°F) 

Measuring interval (TI) 

15 

70 

Integral gain (KI) 

0.2 

0.1 

0.1 

0.2 

0.3 

0.8 

Heating/Reverse 

Cooling/Direct 

100 

T [°C, °F] 
U [V, mA] 

Y

H1

, Y

R1 

X

PH

 

W

X

PC

 

X

DZ

 

Y

C1, 

Y

D1

 

W

X

SBY

 

X

SBY

 

Содержание TCI-W13-H

Страница 1: ...s 1 internal temperature sensor 1 universal input 1 passive input 1 binary output 2 analog outputs Internal temperature sensor standard Add replaceable humidity element as required or order H version...

Страница 2: ...C 212 F 1 K Humidity Sensor AES3 HT Ax Range Measuring Accuracy Hysteresis Repeatability Stability Capacity sensor 0 100 rH See Figure to the right 1 0 1 0 5 year Signal outputs Analog output Output s...

Страница 3: ...or other devices Connection to voltages exceeding 42 V endangers personnel safety 88 3 5 32 1 2 21 0 8 88 3 5 Warning Live electrical components During installation testing servicing and troubleshoot...

Страница 4: ...e memorized and do not need to be re entered Upon return of power Set parameter UP05 to keep the unit off switch on or operation mode before power failure Clock and time schedule settings retained for...

Страница 5: ...yed clock symbol blinks Press OPTION Time schedule status displayed OFF or ON Press OPTION OFF ON blinks UP DOWN to change OPTION to save SEL PRO Pro OFF ON Creating time schedules Step 1 Select a swi...

Страница 6: ...onfiguration AO1 AO2 2 analog outputs DO Binary output configuration do1 1 binary digital outputs relays FU Special functions Common to all TCI How to change parameters 1 Press UP DOWN buttons simulta...

Страница 7: ...FF OFF Celsius UP 08 Show standard display while no key is pressed ON OFF ON UP 09 Select type of content for large digits 00 OFF 0 5 1 01 Input 02 Set point 03 Analog output 04 Binary output 05 Clock...

Страница 8: ...passive temperature NTC or dry contact Match sensor range to input display With a differential pressure transmitter having 0 200 Pa measuring range set UO1 display minimum to 0 and U02 display maximum...

Страница 9: ...limit in heating mode and maximum set point limit in cooling Economy mode may be disabled by setting UP06 to OFF Control loops and sequences are activated when output parameters are defined Cascade co...

Страница 10: ...This is the working range of the proportional control sequence Setting the proportional band to 0 disables proportional control Integral and differential control Proportional control is in most cases...

Страница 11: ...C 1 0 F 1L 22 Switching delay 0 255 s 10 s 1L 23 Activation of reverse direct heat cool sequence OFF activates based on demand ON follows heat cool state of controller Set manually or by auxiliary fun...

Страница 12: ...0 10 VDC default or 0 20 mA Further define analog outputs with A02 Custom ranges can be created by setting minimum and maximum signal limits A control loop special function digital control or analog c...

Страница 13: ...o set output to ON output OFF on conflicting alarms Alarm 1 2 3 4 5 6 7 8 ALA1 ALA8 1d 07 Choose alarm to set output to OFF output OFF on conflicting alarms Alarm 1 2 3 4 5 6 7 8 ALA1 ALA8 1d 08 Displ...

Страница 14: ...onds 0 1275 300 Fu 10 Input limit 1 per input 10 Fu 11 Input limit 2 Per input 90 Summer winter compensation changes the set point due to a change in an input value typically but not limited to an out...

Страница 15: ...mit 2 ON When limit 2 is greater than limit 1 enable when input value is between limit 1 and limit 2 When limit 2 is less than limit 1 enable when input value below limit 2 or above limit 1 ON OFF OFF...

Страница 16: ...mperature we recommend switching to cooling at 28 C 83 F and to heating at 16 C 61 F outdoor temperature These recommendations are given as suggestions The ideal settings may be different on the actua...

Страница 17: ...0 00 0365 V1 0 20200304 Vector Controls GmbH Switzerland Page 17 Subject to alteration Smart Sensors and Controls Made Easy Quality Innovation Partnership Vector Controls GmbH Switzerland info vectorc...

Отзывы: