Menus
33
Värmebaronen Vedolux -350, -450 and -650
Before the boiler is started for the first time, the
requirements for testing or operation must be met.
The following settings must also be set.
Information
Aggregate test
Safety test
Settings
Code
###
A random number is displayed.
Press
and confirm with
.
E N D
01: Language
English [GB]
Language selection.
Step with
or
until the desired language is displayed.
Confirm with
.
02: Boiler set
[°F] 85
To reduce the risk of an over temperature situation, the
boiler power is reduced by approximately 20% if the boiler
temperature exceeds the setpoint by more than 34.7°F.
Factory setting: 185°F
Setting range: 167 – 185°F
03: Exhaust set
[°F] 140
Desired flue gas temperature, TRG.
Factory setting: 356°F
Setting range: 239 – 464°F
04: O2 set
[%] 6.0
Desired O
2
value during firing, affected by the moisture
content of the wood.
Moisture content: Low
⇐⇒
Normal 16 ±8%
⇐⇒
High
O
2
value:
4.0
6.0
8.0
Factory setting: 6.0% Setting range: 4.0 - 8.0%
05:TAD start
[K] 40
Function that checks the fire in the boiler during ignition. If
the fire is sufficient, combustion control is connected. If not,
the boiler is switched off.
Factory setting: 104°F
Setting range: 77 – 257°F
TAD = difference between flue gas and boiler temperatures.
06: Switch-off
O2/TAG
When the wood has been burned up, the boiler is switched
off via the O
2
value or the flue gas temperature.
O
2
:
should be standard
. Produces easier firing and a larger
quantity of charred wood residue.
TAG: recommended only if the wood is bulky or very damp.
Produces a minimum quantity of charred wood residue.
Factory setting: O
2
Settings: O
2
/ TAG
10:V1 altern.air
[%] 45
If the flue gas temperature sensor or O
2
probe is defective, the
primary air is set to this value.
Only for emergency operation.
Factory setting: 45%
Setting range: 0 - 100 %
11:V2 altern.air
[%] 35
If the flue gas temperature sensor or O
2
probe is defective, the
secondary air is set to this value.
Only for emergency operation.
Factory setting: 35 %
Setting range: 0 - 100 %
Settings must only be set by a person with
knowledge about the functions.
After these settings have been set, an aggregate
test and a safety test must be carried out.
Settings