Värmebaronen Vedolux -350, -450 and -650
The test is available only when the boiler is not in
operation.
When the test is carried out, there must not be any
risk of the boiler being overheated.
There must be no fire or embers in the
boiler when calibrating the O
2
probe.
The O
2
probe is calibrated automatically when the
boiler has not been fired for 48 hours and the probe
has been in operation for more than 200 hours since
the previous calibration.
Press
and
at the same time to end the test.
Calibration
[sek] ###
Information
Aggregate test
O2 sensor +
Test end [+&-]
Calibrate, takes 10 minutes
→
No calibration,
on to next test step.
Safety test
Settings
E N D
Exhaust fan +-
Test end [+&-]
: fan started.
: fan stopped.
: next test step.
Load pump +-
Test end [+&-]
: charging pump started.
: charging pump stopped.
: next test step.
Primary motor+-
Test end [+&-]
: primary air damper opened
: primary air damper closed.
: next test step.
Second.motor +-
Test end [+&-]
: secondary air damper opened.
: secondary air damper closed.
: next test step.
C/O contact +-
Test end [+&-]
: relay contacts C - NO close (external heat source off).
: relay contacts C - NC close. (external heat source on).
: next test step.
Door opener -
Test end [+&-]
: open wood hatch’s lock.
: close wood hatch’s lock.
: next test step.
Li-
Test end [+&-]
: display illumination on.
: display illumination off.
: next test step.
Display 1 +-
Test end [+&-]
: indication on.
: indication off.
: next test step.
Display 2 +-
Test end [+&-]
: indication on.
: indication off.
: next test step.
Display 3 +-
Test end [+&-]
: indication on.
: indication off.
: to ‘display when boiler is not in operation’.
Not used!
Aggregate test
Not used!