12
Värmebaronen Vedolux -350, -450 and -650
Installation must take place according
to existing regulations and standards.
• The boiler must be placed indoors in
a boiler room designed to meet the
existing regulations.
• The installation site must withstand the
weight of the boiler, the accumulator tank
and any chimney.
The boiler may be loaded with maximum
220 lb of the chimney’s weight vertically
downwards.
• There must be a fresh air intake with
at least the same area as the chimney.
Any mechanical ventilation in the room
must not create any negative pressure
that disturbs the operation of the boiler.
• The existing standards for minimum
distance to combustible material must
be met.
The minimum distance for removing
the flue gas fan = minimum 4 in
free space behind the flue gas fan.
Ensure that the provisions for sweeping
meet the existing regulations.
• Adjust the foot bolts so that the boiler
is horizontal.
• The flue pipe must be connected
according to existing standards.
It is important for all connection points
and flues not to leak dust and gas.
If the boiler is connected higher up
the chimney than a previous boiler
was connected, the lower, inactive
part must be filled.
• The boiler must be connected to an open
or closed expansion system.
• The boiler must be connected to an
accumulator system. The boiler shall
be operated at nominal output and
charge the accumulator. Output from
the accumulator can be adjusted to
correspond the heat demand. The
installation must have accumulator
control.
• A temperature limiter, thermal valve
(STW), must be fitted.
• No work must take place on the boiler’s
cover plates as it can damage the boiler’s
electrical equipment.
• The boiler is not designed for oxygenated
water. Hard, calcareous water is not
suitable in a plumbing and heating context.
If you have your own well, the water
quality must be checked so that it does
not cause damage. Copper in the pipes
must not be subjected to abnormally
aggressive water. A water analysis will
give you the necessary information.
If the water quality is poor, a water filter
must be installed.
• The turbulators and the draught
damper can be used to adjust the flue
gas temperature if there is a risk of
condensation in the chimney.
• The boiler must be installed in a way
to prevent problems caused by smoke,
the general recommendation is that
the chimney shall be one meter higher
than the highest part of the roof. Avoid
installation in highly urbanized areas, or if
the surrounding buildings are higher than
the chimney.
Installation