28
Värmebaronen Vedolux -350, -450 and -650
Menu system
Exhaust temp.
[°F] ###.#
Operation display
switches off the boiler.
alternating display
Boiler temp.
[°F] ###.#
↓
Selection
Information
↓
↑
press
→
Boiler set
[°F] ---.-
↓
↑
Serial number
########
to proceed, then
or
to step down/
up in the menu.
exits the menu, switches to operation display.
The display returns to operation display if no key
has been pressed for 30 minutes and if a fault or
over temperature occurs.
Selection
Aggregate test
↓
↑
press
→
O2 calib
Test end [+&-]
↓
Display 3 +-
Test end [+&-]
Only available when the boiler is switched off.
/
activates/deactivates the test point.
to next test point.
and
together end the test.
The test is ended with
at the last test point
or if no key has been pressed for 15 minutes.
The display returns to operation display.
Selection
Safety test
↓
↑
press
→
Safety test +
[sec.] 30
↓
↑
Boiler temp.
[°F] ---.-
Only available when the boiler is in operation.
Keep
pressed in or press it every 30 seconds.
The test is limited to 30 minutes.
The test ends and the display returns to operation
display if the boiler temperature exceeds 230°F
or
has not been pressed every 30 seconds.
Selection
Settings
↓
↑
press
→
Code
###
↓
↑
11:V2altern. air
[%] 35
Code =
then
The menu is exited with
at the last test point
or if no key has been pressed for one minute.
The display returns to operation display.
E N D