WRM-10P AND WRM-40 USER’S MANUAL
REV 3
20
3.4
Performing a Resistance Test
a.
Start from the “START-UP” menu:
Press the
[1]
key (
TEST XFMR
).
b.
The following screen will be displayed:
Press the
[1]
key (
V1 & V2 TEST
) if you would like to perform a V1 & V2 test.
Press the
[2]
key (
V1 ONLY TEST
) if you would like to perform a V1 test only.
Please see section 3.5 for information about performing special tests.
NOTE
The test current is 10 Amps for the WRM-10P and 40 Amps for the WRM-40.
c.
The following menu will be displayed:
Press the
[2]
key (
NO
).
d.
The following screen will be displayed:
1.
YES
Press the
[1]
key (
YES
) if you wish to convert readings to standard temperature.
The following screen will be displayed:
LTC or VTG REG?
1.
YES
2.
NO
WINDING MATERIAL:
1.
COPPER, Tk=234.5
2.
ALUMINUM, Tk=225
3.
MANUALLY ENTER Tk
CONVERT READINGS
TO STANDARD TEMP?
1.
YES
2.
NO
1.
V1 & V2 TEST
2.
V1 ONLY TEST
3.
SPECIAL TEST V1,V2
4.
SPECIAL TEST V1
1.
TEST XFMR 11/02/09
2.
SETUP 12:33:01
3.
USER DIAG
Содержание WRM-10P
Страница 12: ...WRM 10P AND WRM 40 USER S MANUAL REV 3 8 Figure 2 WRM 40 Controls and Indicators...
Страница 15: ...REV 3 WRM 10P AND WRM 40 USER S MANUAL 11 Figure 5 WRM 10P Relay Location Figure 6 WRM 40 Relay Location...
Страница 39: ...REV 3 WRM 10P AND WRM 40 USER S MANUAL 35 Figure 14 Typical LTC Voltage Regulator Test Report Printout...
Страница 44: ...WRM 10P AND WRM 40 USER S MANUAL REV 3 40 Figure 15 Typical Five Minute Special Test Report Printout...
Страница 54: ...WRM 10P AND WRM 40 USER S MANUAL REV 3 50 Figure 17 Typical Test Record Directory Printout...